Schneider Electric EZC250H2160

Schneider Electric EZC250H2160 EasyPact EZC250H Circuit Brea

MPN EZC250H2160
Obsolete

Schneider Electric EasyPact EZC250H series, EZC250H2160, 2-pole circuit breaker, 160 A rated current, thermal-magnetic TM-D trip unit, 10-85 kA breaking capacity per IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC250H2160 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

EZC250H2160 additional specifications
ParameterValue
Temp storage min-35 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Depth60 mm
Width105 mm
Height165 mm
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric EZC250H2160 is a 2-pole EasyPact EZC250H circuit breaker rated 160 A at 40 °C (160 A at 50 °C with the TM-D trip unit). That 160 A continuous rating governs the feeder or panelboard main it can protect — size the upstream conductor and downstream load for that ampacity. The thermal-magnetic trip provides both overload (thermal) and short-circuit (magnetic) protection in one unit, so no separate overload relay is needed for distribution circuits. Breaking capacity varies by voltage: 85 kA Icu at 240 V AC, 36 kA at 415 V AC, and 10 kA at 550 V AC. At 250 V DC (2-pole series) it delivers 30 kA Icu. IP20 finger protection and IK07 impact resistance cover panel-mount handling.

For volume purchases or blanket orders, the 160 A TM-D trip unit and 2-pole format are consistent across the EasyPace EZC250H platform, so BOM continuity is straightforward.

The toggle handle provides positive contact indication, so an operator can visually confirm the open/closed state without removing the cover. Connection pitch is 35 mm, matching common DIN-rail terminal block spacing.

Certified to JIS C8201-2-2, EN/IEC 60947-2, and GB/T 14048.2. The IEC 60947-2 listing covers the breaking capacity and isolation suitability. For a liquidation or auction buyer, the compliance documentation (declaration of conformity, CE marking) is standard with the Schneider EasyPact series — no special documentation package is required beyond what ships with the breaker.