Skip to main content
Schneider Electric EZC250N4160

Schneider Electric EZC250N4160 EasyPact EZC250N Circuit Brea

MPN EZC250N4160
Active

Schneider Electric EasyPact EZC250N, thermal-magnetic circuit breaker, 4 poles, 160 A, TM-D trip unit, 20 kA Icu at 440 V AC.

$169.53 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC250N4160 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-35 °C

All specifications

EZC250N4160 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60947
Depth60 mm
Width140 mm
Height165 mm
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric EZC250N4160 is a 4-pole EasyPact EZC250N circuit breaker rated 160 A at 40 °C, with a TM-D thermal-magnetic trip unit.

This breaker is a fixed-mount backplate unit — no DIN-rail clip, so plan for screw-down installation on a panel backplate. Connection pitch is 35 mm, matching standard bus-bar spacing for a 4-pole breaker.

Protection profile and coordination

The TM-D trip unit combines a thermal bimetal for overload protection and a magnetic coil for short-circuit protection. It protects 3 poles with no neutral protection and no built-in earth-leakage module — if you need ground-fault protection, you add an external relay or a different breaker variant. Utilization category A means it's not intended for frequent switching of motor loads under load; it's a distribution breaker, sized for cable and bus protection in a distribution panel. The 10,000-cycle mechanical durability is typical for a panelboard breaker — fine for infrequent switching, not for daily motor starting.

MPN