Skip to main content
Schneider Electric EZC250N44125

Schneider Electric EZC250N44125 EasyPact EZC250N, 125 A, 20

MPN EZC250N44125
Obsolete

Schneider Electric EasyPact EZC250N series, EZC250N44125, 4-pole circuit breaker, 125 A rated current, 20 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, fixed mount, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC250N44125 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

EZC250N44125 additional specifications
ParameterValue
Temp storage min-35 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60947
Depth60 mm
Width140 mm
Height165 mm
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric EZC250N44125 is a 4-pole EasyPact EZC250N circuit breaker with a thermal-magnetic TM-D trip unit, rated 125 A at 40 °C and delivering a 20 kA Icu breaking capacity at 440 V AC. It's built to IEC 60947-2 for distribution duty — the standard that governs molded-case breakers in commercial and industrial panels.

If your panel runs hotter — say 50 °C — the trip unit rating drops to 125 A at 50 °C, meaning the breaker still holds its full rating at that elevated ambient, no derate penalty. That's unusual for a thermal-magnetic; most need a size bump at 50 °C. Breaking capacity varies by voltage: 50 kA at 220–240 V AC, 25 kA at 380–415 V AC, 20 kA at 440 V AC, and 8 kA at 550 V AC. On the DC side, it's 20 kA at 125 V DC (1-pole) and 20 kA at 250 V DC (2-pole). That 690 V Ui tells you the internal creepage and clearance are designed for 690 V systems, even though the breaker's operational rating is 550 V.

This is a fixed-mount breaker on a backplate, not a DIN-rail snap-on. Connection pitch is 35 mm — standard for busbar or cable lug termination in a distribution board.

MPN