Specifications

LC1D65008G6 key specifications
ParameterValue
Control circuit typeAC 60 Hz
Main product or component typeContactor
VoltagePower circuit Power circuit <= 300 V DC
Coil voltage120 V AC 60 Hz
Current80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
Breaking capacity1000 A at 440 V for power circuit conforming to IEC 60947
Utilization categoryAC-1
IP ratingIP20
Temp operating max60 °C
Temp operating min-40 °C
Pollution degree3
Depth4.9 in (125 mm)

All specifications

LC1D65008G6 additional specifications
ParameterValue
Width3.3 in (85 mm)
Height5 in (127 mm)
Electrical life cycles1.4 Mcycles 80 A AC-1 <= 440 V
Mechanical life cycles6 Mcycles
ApplicationResistive load
Fire behaviorV1 conforming to UL 94
Operating time4...19 ms opening 12...26 ms closing
Permissible ambient air temperature around the device-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating

Product details

Part identity and intended use

It is rated at 80 A continuous current at AC-1, with a power circuit impedance of 1.5 mOhm per phase at 50 Hz, giving a per-phase dissipation of 4–5 W at 60 Hz coil excitation. Coil inrush at 60 Hz and 20°C is 140 VA. It is certified to UL 60947-4-1, CSA C22.2 No 14, IEC 60947-4-1, and EN 60947-4-1, covering the main North American and international standards for contactors used in motor and resistive load circuits.

Key ratings and their meaning

The AC-1 rating (80 A) governs its use on resistive loads. Electrical durability is 1.4 Mcycles at that current up to 440 V. Mechanical durability is 6 Mcycles. Operating time: opening 4–19 ms, closing 12–26 ms. Overvoltage category III suits fixed installation. Pollution degree 3 allows for conductive pollution environments. Shock resistance: 8 Gn open, 10 Gn closed; vibration: 2–3 Gn across 5–300 Hz. The coil is AC 60 Hz without built-in suppressor. Inrush power is 140 VA at 60 Hz; heat dissipation during holding is 4–5 W. Control circuit torque 15.05 lbf.in (1.7 N·m); power circuit up to 70.8 lbf.in (8 N·m) depending on conductor size.

The part carries a full set of third-party certifications (UL, CSA, IEC) so replacement with a non-certified alternate is not straightforward. No direct-form-fit-function cross is listed in the official documentation; any cross-sourcing must preserve the 4-pole, 80 A AC-1, 60 Hz coil footprint.

Mounting and terminal integration

Mounting support is rail and plate (sold separately). Front-face protection is IP20. Control terminals accept 1–4 mm². Strip length is per datasheet but the cage accepts 0.2–4 mm² on the control side. Dimensions: width 85 mm, height 127 mm, depth 125 mm.