Skip to main content
Schneider Electric LC1F185FE7

Schneider Electric LC1F185FE7 TeSys F Contactor, 115 V AC Co

MPN LC1F185FE7
Obsolete

Schneider Electric TeSys F LC1F185FE7, 3-pole contactor, 115 V AC 40-400 Hz coil, 275 A AC-3 rated operational current, plate mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LC1F185FE7 key specifications
ParameterValue
Motor starter typeDirect on-line contactor
Control circuit typeAC at 40...400 Hz
Main product or component typeContactor
Voltage690 V AC 50/60 Hz
Coil voltage115 V AC 40...400 Hz
Current275 A (at 185 A (at <55 °C) at <= 440 V AC-3
Breaking capacity1480 A conforming to IEC 60947-4-1
Utilization categoryAC-3 AC-4 AC-1
Temp storage max80 °C
Temp storage min-60 °C
Temp operating max55 °C
Temp operating min-5 °C

All specifications

LC1F185FE7 additional specifications
ParameterValue
Storage temperature-60...80 °C
Depth181 mm
Width168.5 mm
Height174 mm
Mechanical life cycles10 Mcycles
ApplicationResistive load, Motor control
Operating time35 ms closing at Uc) 130 ms opening at Uc)
Operating temperature-5...55 °C
Permissible ambient air temperature around the device-40...70 °C

Product details

The LC1F185FE7: The headline rating is 275 A at ≤ 440 V AC-3 — that is the motor-switching current, not the resistive load rating. AC-3 duty covers starting and running of squirrel-cage motors, so the 275 A figure governs the contactor's ability to handle inrush and break the motor circuit under load. For resistive loads (AC-1), the thermal current Ith is 275 A at 50 Hz with an average impedance of 0.33 mOhm per pole. The motor power table is the practical selection tool: 90 kW at 380-400 V, 100 kW at 415 V, 100 kW at 440 V, 110 kW at 500 V, and 110 kW at 660-690 V — all AC-3. At 220-230 V AC-3 it drops to 55 kW. For AC-4 reversing or inching duty at 400 V, the rating is 33 kW. The 115 V AC control coil (40-400 Hz) pulls 1070 VA inrush at cos φ 0.9; hold-in dissipation runs 8-9.8 W total. The coil pick-up range is 0.85-1.1 Uc, drop-out between 0.2-0.55 Uc — important for brownout ride-through assessment.

The contactor is designed and tested to EN 60947-1, IEC 60947-1, EN 60947-4-1, IEC 60947-4-1, and JIS C8201-4-1. Rated insulation voltage (Ui) is 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 Group C. Overvoltage category III. The rated breaking capacity is 1480 A per IEC 60947-4-1. Protective treatment is TH (tropicalized). Front face with shrouds achieves IP2X per IEC 60529 and VDE 0106. Associated fuse protection: 200 A aM or 315 A gG at ≤ 440 V.

Mechanical & Mounting

Mounting is plate-mount (not DIN rail). Dimensions: 174 mm height, 168.5 mm width, 181 mm depth. Power circuit connections accept bar (25 x 3 mm busbar), ring terminals, or bolted connection for 1 x 150 mm² cable. Control circuit uses screw clamp terminals accepting 1-4 mm² flexible or solid (1 or 2 cables). Tightening torque: 18 N.m on power circuit, 1.2 N.m on control. Mechanical durability is 10 million cycles; maximum operating rate is 2400 cycles per hour at 55 °C. Operating time: 35 ms closing, 130 ms opening at rated control voltage.

Deployment Context

The plate-mount form factor and 275 A AC-3 rating place it in the heavy-duty motor starter class — typically feeding conveyors, pumps, compressors, or large fans on 400-690 V three-phase supplies. The IP2X front face with shrouds provides basic finger protection inside an enclosed panel. The 115 V AC coil is standard for North American and some Asian control voltage schemes.

MPN
LC1F185FE7