Skip to main content
Schneider Electric LC1F2600M7

Schneider Electric LC1F2600M7 TeSys F Contactor, 2600 A AC-1

MPN LC1F2600M7
Obsolete

Schneider Electric TeSys F, contactor, LC1F2600M7, 3-pole, 2600 A AC-1, 220 VAC 40-400 Hz coil, plate mount, IP20 front face.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LC1F2600M7 key specifications
ParameterValue
Control circuit typeAC at 40...400 Hz
Main product or component typeContactor
Voltage<= 1000 V AC 50/60 Hz
Coil voltage220 V AC 40...400 Hz
Insulation voltage ui1000 V conforming to IEC 60947-4-1 1000 V conforming to UL 60947-4-1
Current2600 A (at <60 °C) AC AC-1
Breaking capacity3900 A conforming to IEC 60947-4-1
Utilization categoryAC-1
Temp storage max80 °C
Temp storage min-60 °C
Temp operating max40 °C
Temp operating min-5 °C

All specifications

LC1F2600M7 additional specifications
ParameterValue
Storage temperature-60...80 °C
Depth251 mm
Width519 mm
Height382 mm
ApplicationResistive load
Operating time40...80 ms closing 100...200 ms opening
Operating temperature-5...40 °C
Permissible ambient air temperature around the device-40...60 °C

Product details

Rated Operational Current and Application

The LC1F2600M7: This contactor is rated for a continuous operational current of 2600 A in AC-1 utilization category (resistive load) at up to 60 °C ambient. The AC-1 rating means it is designed for switching resistive loads such as heating elements, lighting banks, or power distribution — not for motor starting (which would be AC-3 or AC-4). The 2600 A figure governs the main power circuit sizing; the associated fuse recommendation is 2500 A gG at ≤ 440 V. For a panel-builder, this dictates busbar cross-section: the power circuit connection accepts a bar with up to 3 cables or a busbar cross-section of 100 x 10 mm.

Control Circuit and Coil Specifications

The control circuit operates on 220 V AC at 40-400 Hz. The coil draws 2500 VA inrush at 20 °C and holds at 45 VA. The operational voltage limits are 0.85 to 1.1 Uc (187 to 242 V AC) at 55 °C; dropout occurs between 0.3 and 0.5 Uc (66 to 110 V AC). The control circuit uses screw clamp terminals accepting 1 to 4 mm² flexible or solid wire. For a commissioning engineer, verifying the control voltage is within these limits is essential to avoid coil burn-out or failure to pick up.

Standards Compliance and Protection

The LC1F2600M7 is certified to EN 60947-4-1, IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, which are the governing standards for contactors and motor-starters. The front face is rated IP20 with shrouds per IEC 60529 and VDE 0106, meaning it provides finger protection but is not sealed against moisture. The protective treatment is TH (tropicalized) for humid environments. For a compliance buyer, the full set of certifications is documented and verifiable.

Mounting and Physical Integration

This contactor is designed for plate mounting — not DIN-rail. The dimensions are 519 mm width, 382 mm height, and 251 mm depth. The power circuit terminals require a tightening torque of 58 N.m, which is substantial and demands a torque wrench during installation. The control circuit terminals require only 1.2 N.m. For a panel OEM, the plate-mount requirement and the large footprint mean enclosure sizing must account for this unit's physical envelope and the busbar bending radius.

Thermal Management and Operating Limits

Total heat dissipation is 40 W, with 250 W per pole in AC-1 duty. The average impedance is 0.1 mOhm at 2600 A and 50 Hz. The rated short-time withstand current (Icw) is 12,000 A for 10 seconds at 40 °C, derating to 4,000 A for 10 minutes. The maximum operating rate is 600 cycles per hour at 55 °C. Ambient temperature range for operation is -5 to 40 °C; storage range is -60 to 80 °C. For a site electrical engineer, these thermal figures determine the need for forced ventilation or derating in high-ambient enclosures.

MPN
LC1F2600M7