Skip to main content
Schneider Electric LC1K0601P5

Schneider TeSys K LC1K0601P5 Contactor, 3P, 6A AC-3, 230V 50

MPN LC1K0601P5
Obsolete

Schneider Electric TeSys K series, LC1K0601P5, 3-pole contactor, 6 A AC-3/AC-3e, 1 NC auxiliary contact, 230 V 50 Hz coil, screw clamp terminals.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LC1K0601P5 specifications
ParameterValue
Main product or component typeContactor
Utilization categoryAC-3 AC-3e AC-4
IP ratingIP20
Temp storage max80 °C
Temp storage min-50 °C
Storage temperature-50...80 °C
Depth57 mm
Width45 mm
Height58 mm
Electrical life cycles1.3 Mcycles 6 A AC-3 at Ue 1.3 Mcycles 6 A AC-3e at Ue 0.05 Mcycles 36 A AC-4 at Ue <= 440 V
Mechanical life cycles10 Mcycles
ApplicationMotor control

Product details

The Schneider Electric LC1K0601P5 is a TeSys K series 3-pole contactor rated for motor control in AC-3 and AC-3e duty at 6 A up to 440 V, with a 230 V 50 Hz coil and one normally closed auxiliary contact. AC-3 is the standard category for starting and stopping squirrel-cage motors — the 6 A rating means it handles motors drawing that current under full-load start, not just resistive loads. The AC-3e variant adds energy-efficiency classification per IEC 60947-4-1. Mechanical durability is 10 million cycles, so the coil and armature outlast the contacts under light duty.

Screw clamp terminals accept 1.5 to 4 mm² solid or 0.34 to 2.5 mm² flexible with ferrules, so it wires into existing panel layouts without adapter blocks. Tightening torque is 0.8 to 1.3 N·m. IP20 finger protection per VDE 0106 means it is safe for open-panel mounting where tools are required to access live parts — standard for enclosed industrial control panels.

Compliance documentation covers EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1, plus IEC 60335-1 Clause 30.2 for appliance applications. Flame retardance is V1 per UL 94. These certifications cover most industrial and commercial installations in North America, Europe, and Japan.

What the auxiliary contact and coil specs mean for the circuit

The single NC auxiliary contact is instantaneous — it changes state with the main poles, no delay. Minimum switching capability is 5 mA at 17 V for signalling circuits, so it works with low-power PLC inputs without wetting current issues. The coil draws 30 VA inrush and 4.5 VA hold-in at 20 °C, dissipating 1.3 W. No built-in suppressor module is fitted, so if the coil is driven by a PLC output or solid-state relay, add a free-wheeling diode or RC snubber across the coil to protect the driver from inductive kickback. Coil dropout threshold is 20% of rated voltage below 50 °C, ensuring reliable release on undervoltage.

MPN
LC1K0601P5