LUCA05BLTQ specifications
ParameterValue
Load type3-phase motor - cooling: self-cooled
Main product or component typeStandard control unit
Voltage690 V AC
Coil voltage24 V DC
Insulation voltage ui690 V conforming to IEC 60947-6-2 600 V conforming to UL 60947-4-1 600 V conforming to CSA C22.2 No 60947-4-1
Utilization categoryAC-43 AC-41 AC-44
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Depth60 mm
Width45 mm
Height66 mm
ApplicationMotor control Motor protection
Fixing modePlug-in (front face)
Operating time35 ms opening with LUB12 for control circuit 35 ms opening with LUB32 for control circuit 35 ms opening with LUB38 for control circuit 70 ms closing with LUB12 for control circuit 70 ms closing with LUB32 for control circuit 70 ms closing with LUB38 for control circuit
Operating temperature-25...70 °C

Product details

The Schneider Electric TeSys U LUCA05BLTQ is a standard control unit for the TeSys U motor starter system. It handles basic motor protection — overload and short-circuit — for a 3-phase motor, self-cooled. At 400...440 V AC 50/60 Hz it's rated for 1.5 kW motor power; at 500 V AC that climbs to 2.2 kW, and at 690 V AC to 3 kW. The tripping threshold is fixed at 14.2 x Ir, with a ±20% tolerance, and it's Class 10 thermal overload. The control voltage limits are 20...27 V DC for operation, with dropout at 14.5 V DC — so a saggy 24 V supply won't cause nuisance dropouts unless it dips below that floor.

Where it lives in the panel

The control unit itself is IP20 on the front panel and wired terminals, IP40 on other faces outside the connection zone. The unit plugs into the front face of the power base, so it's a snap-in swap without disturbing the load wiring. Physical footprint is 45 mm wide, 66 mm tall, 60 mm deep — it tucks into a standard DIN-rail layout without hogging space. Operating altitude tops out at 2000 m, so if you're building a panel for a high-altitude installation, you'll need to derate or choose a different variant.

The utilisation categories are AC-41 (resistive), AC-43 (motor starting, plugging, inching), and AC-44 (motor switching with frequent starts). It's phase-failure sensitive — it will trip if one phase drops out, which is a common failure mode that cooks motors. Earth fault protection is also built in. The immunity to microbreaks is 3 ms, meaning a brief power glitch shorter than that won't cause a nuisance trip.

MPN