Skip to main content
Schneider Electric LUCA1XBLTQ

Schneider TeSys U LUCA1XBLTQ Standard Control Unit, 24 V DC

MPN LUCA1XBLTQ
Obsolete

Schneider Electric TeSys U standard control unit, LUCA1XBLTQ, 24 V DC coil, 0.25 kW at 400-440 V AC, Class 10 thermal overload, IP20 front panel.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LUCA1XBLTQ specifications
ParameterValue
Load type3-phase motor - cooling: self-cooled
Main product or component typeStandard control unit
Voltage690 V AC
Coil voltage24 V DC
Insulation voltage ui690 V conforming to IEC 60947-6-2 600 V conforming to UL 60947-4-1 600 V conforming to CSA C22.2 No 60947-4-1
Utilization categoryAC-43 AC-41 AC-44
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Depth60 mm
Width45 mm
Height66 mm
ApplicationMotor control Motor protection
Fixing modePlug-in (front face)
Operating time35 ms opening with LUB12 for control circuit 35 ms opening with LUB32 for control circuit 35 ms opening with LUB38 for control circuit 70 ms closing with LUB12 for control circuit 70 ms closing with LUB32 for control circuit 70 ms closing with LUB38 for control circuit
Operating temperature-25...70 °C

Product details

The Schneider Electric LUCA1XBLTQ is a standard control unit for the TeSys U motor-starter system. It provides basic protection against overload, short-circuit, phase failure, phase imbalance, and earth faults for a 3-phase motor load. Rated for a 0.25 kW motor at 400...440 V AC 50/60 Hz, it uses a 24 V DC control circuit and draws 60 mA sealed (80 mA with LUB32 or LUB38 control modules) and up to 130-220 mA during closing, depending on the control module fitted.

Thermal overload class is Class 10 with temperature compensation from -25 to 70 °C per IEC 60947-6-2 and UL 508. Utilisation categories AC-41, AC-43, and AC-44 cover switching and protection of motor loads under normal and occasional overload conditions. AC-44 is the most demanding — it certifies the unit for frequent inching and plugging duty, not just simple on-off motor starting. Tripping threshold is 14.2 x Ir ± 20 % for magnetic short-circuit protection. Rated insulation voltage is 690 V per IEC 60947-6-2, and 600 V per UL 60947-4-1 and CSA C22.2 No 60947-4-1.

Where this class of part is used

The TeSys U system is a modular motor starter that combines a power base, control unit, and communication or auxiliary modules in a single DIN-rail footprint. The LUCA1XBLTQ control unit plugs into the front of the power base and handles the protection logic and coil control. It is designed for motor control panels in industrial machinery, conveyors, pumps, fans, and compressors where a compact, coordinated motor starter with overload and short-circuit protection is needed. The plug-in design means the control unit can be swapped without rewiring the power base.

MPN
LUCA1XBLTQ