Skip to main content
Schneider Electric LV838923

Schneider Electric LV838923 MasterPact MTZ2, 2000 A, 3P, Obs

MPN LV838923
Active

Schneider Electric MasterPact MTZ2, LV838923, 3-pole drawout circuit breaker, 2000 A rated, LF breaking capacity, 600 VAC, UL 489.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV838923 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Terminal pitch4.5 in (115 mm)
Depth16.8 in (426.8 mm)
Width17.5 in (444.3 mm)
Height17.3 in (438.8 mm)
ApplicationProtection
Safety category200 kA Icu 240 V AC 50/60 Hz UL 489 150 kA Icu 480 V AC 50/60 Hz UL 489 100 kA Icu 600 V AC 50/60 Hz UL 489

Product details

The Schneider Electric LV838923 is a MasterPact MTZ2 drawout circuit breaker, 3-pole, rated 2000 A at 40 °C, with an LF breaking capacity code. The integral instantaneous protection trips between 49.5 and 55.5 kA — that's the magnetic-only pickup range for bolted faults. Below that, the 22 kA short-time withstand (Icw) for 0.5 s per UL 489 lets the breaker ride through downstream faults long enough for a feeder breaker to clear, preserving selectivity. Drawout mounting means the breaker chassis stays bolted to the base plate rails, and the removable cradle slides in and out for safe maintenance or swap without disturbing the bus connections. The 4.5 in (115 mm) connection pitch matches standard panel bus spacing for this frame size.

Sourcing reality — lifecycle and procurement posture

This part is officially obsolete per the manufacturer. If your design is still in the specification phase, this is the moment to evaluate a current-production MasterPact MTZ frame with a similar rating to avoid a future last-time-buy scramble.

The breaker occupies a 17.5 in wide by 17.3 in tall by 16.8 in deep footprint. That depth includes the drawout mechanism and arc chute — verify your enclosure depth allows the full 426.8 mm for the cradle plus clearance for the rear bus connections and any auxiliary wiring trough. The base plate rails are the intended mounting support; no additional sub-panels needed for this frame.

MPN