Schneider Electric LV839031 MasterPact MTZ3, 5000 A, 3P Draw

MPN LV839031
Active

Schneider Electric MasterPact MTZ3 ANSI circuit breaker, LV839031, 3-pole drawout, 5000 A rated at 40 °C, H3 breaking capacity (100 kA Icu at 508 V), without Micrologic trip unit.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV839031 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Terminal pitch9.06 in (230 mm)
Depth16.8 in (426.8 mm)
Width31.07 in (789.1 mm)
Height18.8 in (478.1 mm)
Electrical life cycles2800 cycles ANSI C37.50
Mechanical life cycles12500 cycles ANSI C37.50
ApplicationProtection
Safety category100 kA Icu 254 V AC 50/60 Hz ANSI C37.50 100 kA Icu 508 V AC 50/60 Hz ANSI C37.50 85 kA Icu 635 V AC 50/60 Hz ANSI C37.50

Product details

The LV839031 is a Schneider Electric MasterPact MTZ3 ANSI power circuit breaker, rated 5000 A at 40 °C, 3-pole, drawout-mounted, with H3 breaking capacity code. It is built for main or feeder protection in 635 VAC switchgear, delivering 100 kA Icu at 508 VAC and 85 kA Icu at 635 VAC per ANSI C37.50. This variant ships without a Micrologic trip unit — you select and install the protection relay separately, matching the trip curve to your coordination study.

Breaking performance and selectivity headroom

The H3 breaking capacity code on this MTZ3 50 H3 means 100 kA Icu at 254 VAC and 508 VAC, and 85 kA Icu at 635 VAC — all per ANSI C37.50. That puts it in the high-interrupting tier for industrial switchgear where fault currents exceed 65 kA. The rated short-time withstand (Icw) is 85 kA for 0.5 s, which supports delayed-tripping coordination downstream without the breaker sacrificing itself during a through-fault. Integral instantaneous protection triggers between 171 and 209 kA, a narrow band that avoids nuisance trips on motor-start inrush while still clearing a bolted fault fast.

Physical footprint and drawout integration

At 31.07 in wide, 18.8 in tall, and 16.8 in deep, this drawout breaker occupies a full cubicle compartment in standard ANSI switchgear. The drawout mechanism (racked in/out without unbolting power conductors) lets you isolate the breaker for maintenance or replacement while the bus remains live — critical for continuous-process plants where a full bus outage is unacceptable. Mounting support is base plate rails; connection pitch is 9.06 in (230 mm) between phases. Plan for a dedicated compartment with rear-accessible primary disconnects and a separate control wiring trough for the trip unit interface.

Electrical durability is 2800 cycles under ANSI C37.50, and mechanical durability is 12500 cycles; that is a maintenance-cycle breaker, not a daily-switching device. The 25 to 30 ms maximum breaking time means it clears a fault within 3 cycles at 60 Hz, fast enough to limit let-through energy on downstream equipment. Maximum closing response is 70 ms, which matters when synchronizing with auto-transfer schemes.