Schneider Electric MasterPact MTZ2 LV846164, 2000 A, 100 kA

MPN LV846164
Active

Schneider Electric MasterPact MTZ2, LV846164, 3P fixed circuit breaker, 2000 A rated current, 100 kA breaking capacity at 440 V AC, H2V performance level.

$6,075.54 – $15,112.99 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846164 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846164 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width422 mm
Height352 mm
Electrical life cycles8000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 8000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The LV846164 is a fixed-mount MasterPact MTZ2 circuit breaker, 3-pole, rated 2000 A at 40 °C. That 2000 A continuous current handles the main feed of a large distribution board or a high-load industrial bus. The H2V performance grade delivers 100 kA ultimate breaking capacity (Icu) at 440 V AC — enough to clear a bolted fault on a transformer secondary without upstream coordination issues. Category B selectivity means it holds full discrimination with downstream breakers, so a fault on a branch won't drop the main. The short-time withstand (Icw) is 100 kA for 0.5 s and 1 s, and 75 kA for 3 s — that's the thermal and dynamic stress the breaker can carry during a delayed trip. For selective coordination schemes where the main breaker waits for a downstream device to clear, this Icw rating is the number that governs. The making capacity (Icm) of 220 kA at 440 V AC confirms the contacts can close into a fault without welding. Mounting is fixed on rails or a base plate, with front or rear connections on both the line and load sides. The 422 mm width, 352 mm height, and 300 mm depth fit a standard switchboard cubicle — plan for the 115 mm connection pitch when laying out busbars. IP30 protection suits indoor panel installation; no additional enclosure needed for dust or drip protection.

Standards and compliance — what the approvals cover

The breaker complies with EN/IEC 60947-1 (general rules), EN/IEC 60947-2 (circuit breakers), and EN/IEC 60947-2 Annex H (selective breakers). It also meets IEC 61557-12 for performance measurement in power distribution.

Durability and thermal — cycles and dissipation

Mechanical durability is 15,000 cycles with periodic preventive maintenance. Electrical durability under AC-23A (frequent switching of motor loads) is 8,000 cycles at 440 V AC and rated current; under AC-3 (direct switching of motors) it is 6,000 cycles. Power dissipation at rated current is 250 W — factor that into cabinet ventilation calculations.