Skip to main content
Schneider Electric LV846165

Schneider Electric LV846165 MasterPact MTZ2 2500 A Circuit B

MPN LV846165
Active

Schneider Electric MasterPact MTZ2, fixed circuit breaker, 3P, 2500 A at 40 °C, H2V 100 kA at 415 V AC, IP30.

$8,505.81 – $15,112.99 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846165 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846165 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width422 mm
Height352 mm
Electrical life cycles5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The Schneider Electric LV846165 is a MasterPact MTZ2 fixed-mount, three-pole circuit breaker rated for 2500 A at 40 °C, with a 100 kA ultimate breaking capacity (Icu) at 440 V AC. It sits in the MasterPacT range and is designed for main or feeder protection in power distribution — think switchboards, generator incomers, or large motor control center mains where you need Category B selectivity (meaning it can discriminate with downstream devices to keep the rest of the plant live during a fault).

The Icu of 100 kA at both 220/415 V and 440 V AC means this breaker clears a 100 kA fault without damage; the Ics (service breaking capacity) is the same 100 kA, so after clearing a fault at that level it can be reclosed and carry load again — not all breakers match Ics to Icu. The Icw (short-time withstand) of 100 kA for 1 second is what enables the selectivity coordination: downstream breakers have time to clear before this one trips. The 12 kV impulse withstand (Uimp) covers surge environments typical of industrial distribution.

Fixed-mount design — no draw-out cradle. It bolts to a base plate or rails (mounting support listed as rails/base plate). Dimensions: 422 mm wide, 352 mm high, 300 mm deep. Connection pitch is 115 mm, and both upside and downside connections accept front or rear terminations, which gives flexibility in cabinet layout — rear connection keeps busbars behind the breaker, front connection simplifies cable landing. IP30 protection means it is suited for enclosed switchgear; not for washdown environments.

The LV846165 carries approvals to EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H (for selectivity), and IEC 61557-12 (for power metering — relevant if you fit the optional control unit). No RoHS/REACH conflict is expected for this class of industrial gear, but confirm with the factory declaration if your compliance audit requires it.

MPN