Schneider Electric MasterPact MTZ2, fixed 4-pole circuit breaker, 2000 A rated current at 40 °C, H2V 100 kA at 415 V AC performance type, LV846184.

$7,898.04 – $14,447.73 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846184 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846184 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
Electrical life cycles8000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 8000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The LV846184 is a fixed-mount, 4-pole MasterPact MTZ2 air circuit breaker from Schneider Electric, built for power distribution protection in industrial and commercial switchboards. It's a Category B breaker — meaning it's fully selective with downstream devices, so a fault on a branch won't take the whole main bus down. Rated 2000 A at 40 °C ambient, with a sensor range covering 1000 A, 1250 A, 1600 A, and 2000 A, so you can dial in the protection setting to match the load without swapping hardware.

This H2V performance variant delivers 100 kA Icu (ultimate breaking capacity) at 415 V AC, and the same 100 kA Ics (service breaking capacity) at both 220/415 V and 440 V AC — meaning after clearing a fault at its full rating, the breaker is still fit to carry rated current and be reclosed. Short-time withstand (Icw) is 100 kA for 1 second, 75 kA for 3 seconds — critical for selective coordination with downstream feeders.

Standards and physical fit

IP30 front face protection. Dimensions: 537 mm wide, 352 mm high, 300 mm deep. Fixed mounting on rails or base plate. Both front and rear connection options on the upside and downside. Neutral pole on the left.

Durability and environment

Mechanical endurance is 15,000 cycles with periodic preventive maintenance. Electrical durability at rated current: 8,000 cycles at 440 V AC under AC-23A (motor switching), 6,000 cycles under AC-3 (high-frequency motor starting). Maximum breaking time is 25 ms, closing response time 70 ms. Power dissipation at rated current is 250 W — plan for ventilation in the enclosure. Altitude derating above 2000 m.