Skip to main content
Schneider Electric LV846195

Schneider Electric LV846195 MasterPact MTZ2 2500 A Circuit B

MPN LV846195
Active

Schneider Electric MasterPacT MTZ2, LV846195, 4P drawout circuit breaker, 2500 A at 40 °C, H2V 100 kA 415 V AC performance class.

$11,204.46 – $19,431.93 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846195 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846195 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth403 mm
Width556 mm
Height439 mm
Electrical life cycles5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The Schneider Electric LV846195 is a MasterPact MTZ2 drawout circuit breaker, 4-pole, rated 2500 A at 40 °C with a H2V performance class delivering 100 kA breaking capacity at 415 V AC. It sits in the MasterPacT range, designed for power distribution protection in commercial and industrial switchboards where you need Category B selectivity — meaning it coordinates with downstream breakers to isolate only the faulted circuit, keeping the rest of the plant live.

The Icw of 100 kA for 1 second gives you headroom for short-time delay coordination with downstream feeders. Maximum breaking time is 25 ms, closing response 70 ms, so it's fast enough for arc-flash mitigation schemes but deliberate enough for zone-selective interlocking.

Drawout mounting on rails or base plate. Dimensions: 556 mm wide, 439 mm high, 403 mm deep. Connection pitch is 115 mm. Upside and downside connections both offer front or rear termination — gives panel builders flexibility for cable entry and busbar layout. IP30 protection means it's for indoor switchgear, not washdown areas.

Also complies with IEC 61557-12 for measuring equipment.

MPN
LV846195