Skip to main content
Schneider Electric LV846200

Schneider Electric LV846200 MasterPact MTZ2 800A 4P Circuit

MPN LV846200
Active

Schneider Electric MasterPact MTZ2 fixed circuit breaker, LV846200, 800 A at 40 °C, 4 poles, H2V 100 kA 415 V AC, Category B, IP30.

$4,422.87 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846200 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846200 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
Electrical life cycles10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The LV846200 is a MasterPact MTZ2 fixed-mount circuit breaker rated 800 A at 40 °C with a service breaking capacity of 100 kA at 440 V AC. The H2V performance class confirms the 100 kA rating at 415 V AC, so you're covered across the common 400 V class supply voltages. Category B selectivity means the breaker has intentional short-time delay, so it coordinates with downstream devices: a fault on a branch feeder trips the branch breaker first, not this main. That avoids a full panel blackout for a single load fault. The 4-pole design with neutral on the right suits 3-phase + N distribution. Fixed mounting on rails or base plate with front and rear connection options gives flexibility for panel layout — the 115 mm connection pitch matches standard busbar spacing.

IP30 keeps fingers out but expects enclosure protection against water.

Durability and thermal budget

Mechanical durability of 15,000 cycles with periodic preventive maintenance and electrical durability of 10,000 cycles at rated current under AC-23A. Maximum breaking time of 25 ms and closing response time of 70 ms are within typical main-breaker coordination windows.

MPN
LV846200