Skip to main content
Schneider Electric LV846207

LV846207 MasterPact MTZ2 4000A Circuit Breaker, 100 kA

MPN LV846207
Active

Schneider Electric MasterPact MTZ2, LV846207, 4P fixed circuit breaker, 4000 A at 40 °C, H2V 100 kA at 415 V AC, 537 x 352 x 300 mm.

$20,929.59 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846207 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846207 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
Electrical life cycles5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

What this MasterPact MTZ2 carries

The LV846207 is a MasterPact MTZ2 4P fixed circuit breaker rated 4000 A at 40 °C, with an H2V performance class delivering 100 kA breaking capacity at 415 V AC. It is a Category B breaker (selectivity type) per EN/IEC 60947-2, meaning it coordinates with downstream devices to isolate only the faulted branch during a short circuit — critical for maintaining power to healthy loads in a distribution panel.

Breaking capacity and fault handling

Rated service breaking capacity (Ics) is 100 kA at both 220/415 V AC and 440 V AC, so the breaker can clear a fault and be reclosed without replacement. Short-time withstand (Icw) holds 100 kA for 1 second — enough for selective coordination with upstream gear. Making capacity (Icm) reaches 220 kA at 440 V AC, covering the peak asymmetrical current on a bolted fault. Maximum total break time is 25 ms; closing response is 70 ms.

Fixed-mount chassis, 537 mm wide x 352 mm high x 300 mm deep. Connection pitch is 115 mm. Both upside and downside connections accept front or rear terminations — choose based on switchboard bus run. Mounting support is rails or base plate; neutral is on the right. IP30 enclosure suits indoor switchgear; pollution degree 3 per IEC 60947-1 means it tolerates conductive dust in industrial environments.

MPN