Skip to main content
Schneider Electric LV846212

LV846212 MasterPact MTZ2 4P Drawout, 1250 A, 100 kA

MPN LV846212
Active

Schneider Electric MasterPacT, MasterPact MTZ2, circuit breaker, LV846212, 4P, 1250 A at 40 °C, H2V 100 kA at 415 V AC, drawout mounting.

$5,319.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846212 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846212 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth403 mm
Width556 mm
Height439 mm
Electrical life cycles10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The LV846212 is a MasterPact MTZ2 4-pole drawout circuit breaker rated 1250 A at 40 °C. For selectivity coordination, Category B means it has intentional short-time delay, so downstream breakers trip first; the 100 kA Icw for 1 second gives the time margin to achieve full discrimination in a distribution panel.

Deployment context

Drawout mounting means the breaker chassis stays wired in the switchgear while the moving portion racks out for maintenance or replacement — standard for main and tie breakers in 400 V to 690 V industrial distribution where uptime matters. The 403 mm depth and 556 mm width fit standard low-voltage switchgear cubicles; connection pitch is 115 mm. Front and rear connection options allow either cable or busbar entry without reconfiguring the cradle.

Rated for isolation — the open contacts provide a visible gap that meets the safety disconnection requirement. IP30 enclosure protection keeps tools and fingers out but is not washdown-rated; the breaker lives inside a switchgear cubicle, not on the open floor.

Electrical durability and thermal budget

Electrical durability: 10,000 cycles at 440 V AC, 50/60 Hz at In per EN/IEC 60947-2 AC-23A, and 6,000 cycles per AC-3. Mechanical durability is 15,000 cycles with periodic preventive maintenance. Maximum breaking time is 25 ms; closing response is 70 ms. Power dissipation at rated current is 230 W — factor that into the cubicle ventilation calculation.

MPN