Skip to main content
Schneider Electric LV846345

LV846345 MasterPact MTZ2 40HH Switch Disconnector, 4000A

MPN LV846345
Active

Schneider Electric MasterPact MTZ2 40 HH switch disconnector, LV846345, 4000 A rated operational current, 100 kA breaking capacity at 440 V AC, 4 poles, fixed mounting, IP30.

$18,427.50 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846345 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage440 V AC 50/60 Hz conforming to EN/IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to EN/IEC 60947-3
Current4000 A AC 50/60 Hz 440 V
Breaking capacity100 kA Icu at 220/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilization categoryAC-23 A AC-3
IP ratingIP30
Terminal pitch115 mm
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

LV846345 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-4-1
Depth300 mm
Width537 mm
Height352 mm
Electrical life cyclesAC-23 A: 5000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance conforming to EN/IEC 60947-3
ApplicationDistribution
Safety categoryHH
Operating temperature-25...70 °C

Product details

The LV846345 is a MasterPact MTZ2 40 HH switch disconnector rated for 4000 A continuous current at 440 V AC, with a 100 kA Icu breaking capacity at 440 V AC 50/60 Hz per EN/IEC 60947-2. It is a 4-pole, fixed-mount unit with a push-button control and a visible contact position indicator, confirming suitability for isolation per EN/IEC 60947-3.

Rated service breaking capacity Ics matches Icu at 100 kA across both 220/415 V and 440 V — meaning the switch can be reclosed after a fault at full rated short-circuit current without derating. The short-time withstand Icw is 75 kA for 3 s or 100 kA for 1 s, which gives selectivity headroom for downstream breakers in a distribution panel. The making capacity Icm peaks at 220 kA at 440 V, covering the worst-case asymmetric fault closure.

Fixed-mount chassis, 537 mm wide × 352 mm high × 300 mm deep, with a 115 mm connection pitch.

MPN
LV846345