Skip to main content
Schneider Electric LV846551

Schneider Electric LV846551 MasterPact MTZ2, 1000 A, 4P, H10

MPN LV846551
Active

Schneider Electric MasterPact MTZ2, fixed circuit breaker, 4P, 1000 A at 40 °C, H10 50 kA at 1150 V AC, rear connections, push-button control.

$13,755.05 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846551 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage1150 V AC 50/60 Hz
Insulation voltage ui1250 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topRear
Connection surface bottomRear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846551 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
Electrical life cycles500 cycles 1150 V AC 50/60 Hz conforming to EN/IEC 60947-2
Mechanical life cycles25000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

MasterPact MTZ2 — the 1000 A fixed breaker for main switchboard duty

The Schneider Electric LV846551 is a MasterPact MTZ2 fixed circuit breaker, 4 poles, rated 1000 A at 40 °C. It carries an H10 performance class: 50 kA rated service breaking capacity (Ics) at 1150 V AC 50/60 Hz, with a rated short-circuit making capacity (Icm) of 105 kA at the same voltage. That 50 kA Ics at 1150 V means it clears a fault at full rated voltage without needing to trip upstream — the breaker itself handles the interruption, so downstream coordination holds. This is a Category B breaker, which means it is designed for selectivity in distribution — it withstands a short-time current (Icw) of 50 kA for up to 3 seconds, allowing downstream devices to clear a fault first before this unit trips. That 3-second withstand window is what makes selective coordination practical in a main or tie breaker position. Mounting is fixed on rails or a base plate, with rear connections both upside and downside — typical for switchboard builders who want bus-bar stabs rather than cable lugs. The 115 mm connection pitch matches standard MasterPact MTZ bus-bar spacing.

Rated operational voltage (Ue) is 1150 V AC 50/60 Hz, with an insulation voltage (Ui) of 1250 V AC and impulse withstand (Uimp) of 12 kV. If the switchboard ambient runs hotter (say 50 °C), expect a derating curve — typical MasterPact MTZ2 guidance is to reduce by about 1% per degree above 40 °C. The sensor rating range of 400 A, 630 A, 800 A, and 1000 A means the breaker can be re-rated by swapping the electronic trip unit sensor, not the entire frame. Mechanical durability is 25,000 cycles with periodic preventive maintenance; electrical durability is 500 cycles at 1150 V AC. For a main breaker that operates a few times a year, that electrical endurance is effectively life-of-installation. For a breaker that sees frequent switching (e.g., capacitor bank or generator coupling), the 500-cycle figure is a real limit — plan for a contact inspection or replacement at that interval.

Lifecycle and sourcing — active, but plan ahead

For a critical-spare holding or a new switchboard project, it is worth getting a quote locked in early — the 1000 A H10 variant is a common spec, but lead times can stretch when global demand for MTZ2 frames is high.

Physical integration — what fits where

IP30 protection is standard for enclosed switchgear. Altitude derating starts above 2000 m. The neutral position is left — important when phasing bus-bar runs in a 4-pole switchboard. Control is via push-button and the breaker ships without a control unit, meaning the electronic trip unit (Micrologic X or similar) is ordered separately. Factor that into your BOM: the LV846551 is the frame and mechanism only.

MPN
LV846551