Skip to main content
Schneider Electric LV848183

Schneider Electric LV848183 MasterPact MTZ2 08 H1, 800 A, 66

MPN LV848183
Active

Schneider Electric MasterPact MTZ2 series, fixed circuit breaker LV848183 (MTZ2 08 H1), 4-pole, 800 A at 40 °C, H1 performance 66 kA Ics at 415 V AC, Category B selectivity.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848183 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV848183 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
Electrical life cycles10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23 A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3
Mechanical life cycles25000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The LV848183 is a MasterPact MTZ2 08 H1 fixed circuit breaker rated 800 A at 40 °C, meaning it carries continuous load up to that current without tripping — the real-world sizing anchor for a main or feeder breaker in a 690 V AC distribution board. The H1 performance tier delivers 66 kA Ics across the full voltage range from 220/415 V up to 660/690 V AC, so the breaker clears faults up to that level and stays operational afterward — no need to replace after a short-circuit event within that rating. Category B selectivity means the breaker is designed to coordinate with downstream devices so only the faulted branch opens, keeping the rest of the bus live.

Deployment and integration

Fixed mounting on rails or a base plate with front and rear connection options on both upside and downside. IP30 protection means it's suited for indoor switchgear enclosures where tools or fingers are the main concern — not washdown environments. Neutral position on the right matters when laying out the busbar order in a 4-pole assembly.

MPN
LV848183