Skip to main content
Schneider Electric LV848193

LV848193 MasterPact MTZ2 4000 A Circuit Breaker, 66 kA

MPN LV848193
Active

Schneider Electric MasterPact MTZ2, LV848193, 4P fixed circuit breaker, 4000 A rated current, H1 66 kA at 415 V AC, push-button control, IP30.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848193 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch150 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV848193 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
Mechanical life cycles20000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The LV848193 is a MasterPact MTZ2 4P fixed circuit breaker rated 4000 A at 40 °C, with an H1 performance class delivering 66 kA Ics across the full voltage range up to 690 V AC. Selectivity category B means it coordinates with downstream breakers for selective tripping — the faulted branch clears while upstream stays closed. Rated insulation voltage is 1000 V AC, impulse withstand 12 kV. The 66 kA Icw for 3 s means it can carry a short-circuit current for that duration without damage — critical for downstream coordination studies.

Fixed mounting on rails or base plate. Dimensions: 537 mm wide × 352 mm high × 300 mm deep. Connection pitch 150 mm. Upside and downside connections both accept front or rear termination — panel layout flexibility for top-feed or bottom-feed bus runs. Neutral position on the right. IP30 enclosure protection; pollution degree 3 per IEC 60947-1.

Durability and environmental range

Mechanical durability 20,000 cycles with periodic preventive maintenance. Electrical durability: 6000 cycles AC-3 at 440/690 V, 5000 cycles at 440 V per EN/IEC 60947-2. Maximum breaking time 25 ms; closing response time 70 ms. Power dissipation 650 W at rated current — factor into enclosure thermal calculations. Altitude 0–2000 m without derating, 2000–5000 m with derating.

MPN