Skip to main content
Schneider Electric LV848332

Schneider Electric LV848332 MasterPact MTZ2 4000 A Drawout C

MPN LV848332
Active

Schneider Electric MasterPacT MTZ2, LV848332, 4P drawout circuit breaker, 4000 A at 40 °C, H1 66 kA 415 V AC, Category B, IP30.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848332 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch150 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The Schneider Electric LV848332 is a MasterPacT MTZ2 drawout circuit breaker rated 4000 A at 40 °C, 4 poles, with an H1 performance class delivering 66 kA Ics across the full 415 V to 690 V AC range. Category B selectivity means it coordinates with downstream breakers to isolate only the faulted branch — critical for maintaining uptime on a distribution bus feeding multiple loads. This is a drawout-mount breaker (with chassis: 403 mm deep, 556 mm wide, 439 mm high; without chassis: 300 mm deep, 493 mm wide, 300 mm high), designed for switchboard installation where the breaker can be racked out for maintenance without de-energizing the bus.

Breaking capacity and withstand

Rated service breaking capacity Ics is 66 kA at 220/415 V, 440 V, 500/525 V, and 660/690 V AC — flat across the voltage band, so no derating needed as you move up to 690 V. The rated short-time withstand Icw holds 66 kA for 3 seconds, giving downstream protection devices time to clear a fault before the main breaker trips. Making capacity Icm is 145 kA at all listed voltages. Maximum breaking time is 25 ms; maximum closing response time is 70 ms.

Standards compliance includes EN/IEC 60947-1, EN/IEC 60947-2 (including Annex H for EMC), and IEC 61557-12 for power metering.

Drawout mounting with front or rear connection on both upside and downside. Connection pitch is 150 mm. Mounting support options include rails or base plate. Neutral position is on the right. IP30 protection per EN 60529 — suitable for enclosed switchgear, not for washdown environments. Operating altitude 0–2000 m without derating, 2000–5000 m with derating. Power dissipation is 900 W at rated current.

Durability and ratings

Electrical durability varies by duty: 6000 cycles at 440/690 V AC in AC-3 (motor switching), 5000 cycles at 440 V in AC-1 (resistive), 2500 cycles at 690 V in AC-23A (high-stress motor or mixed loads). Sensor rating options cover 2000 A, 2500 A, 3200 A, and 4000 A — the 4000 A frame allows future upsizing without swapping the breaker chassis.

MPN