Skip to main content
Schneider Electric MGN60523

MGN60523 C60N MCB, 2P D-curve 16 A, 20 kA breaking capacity

MPN MGN60523
Obsolete

Schneider Electric Multi9 C60N, miniature circuit breaker, 2P, D-curve, 16 A rated current, 20 kA Icu at 240 V AC, thermal-magnetic trip, 35 mm DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60523 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Breaking capacity20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C

All specifications

MGN60523 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The MGN60523 is a Schneider Electric C60N miniature circuit breaker from the Multi9 range, built for distribution duty in 50/60 Hz AC networks. It's a 2-pole unit rated 16 A at 50 °C with a D-curve — magnetic trip at 12 x In, so it handles the inrush of motor loads, transformers, or welding gear without nuisance tripping on startup. Breaking capacity is the headline here: 20 kA Icu at 240 V phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V, all per EN/IEC 60947-2. The service breaking capacity (Ics) is 75 % of Icu — 15 kA at 240 V, 7.5 kA at 415 V — so after clearing a high-energy fault it's still usable, not a one-shot part. Thermal-magnetic trip technology covers both overload (thermal bimetal) and short-circuit (magnetic solenoid). The D-curve's 12 x In magnetic threshold means a 192 A instantaneous trip — sized for the inductive kick of a small motor or a control transformer bank. Rated operational voltage is 440 V AC max, so it's fine for 400 V three-phase distribution panels.

Width is 36 mm (4 x 9 mm pitches), height 81 mm, depth 73 mm. Wire strip length 14 mm.

What the D-curve and ratings mean for selectivity

D-curve at 12 x In gives you headroom for coordination with downstream C-curve MCBs. In a typical sub-distribution board feeding motor starters, this 16 A D-curve upstream of a 6 A C-curve for a contactor coil holds selectivity up to about 6 kA — the downstream breaker clears the fault before the upstream trips. Pollution degree 3 (industrial environment) and category A (non-selectivity for short-circuit) per 60947-2. Electrical endurance rated at 10,000 cycles, mechanical at 20,000 cycles.

MPN
MGN60523