Skip to main content
Schneider Electric MGN60872

MGN60872 C60N MCB, 1P C-curve 40 A, 10 kA

MPN MGN60872
Obsolete

Schneider Electric Multi9 C60N, MGN60872, 1-pole miniature circuit-breaker, C-curve, 40 A rated current, 10 kA breaking capacity at 240 V AC, EN/IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60872 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage240 V AC 50/60 Hz phase to neutral
Breaking capacity10 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 3 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C

All specifications

MGN60872 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The MGN60872 is a Schneider Electric C60N miniature circuit-breaker from the Multi9 range — 1-pole, C-curve, rated 40 A at 50 °C per EN/IEC 60947-2.

Thermal-magnetic trip with a C-curve: the thermal bimetal protects against sustained overloads, the magnetic coil clears short-circuits. At 8.5 x In (340 A instantaneous pickup for this 40 A unit), it avoids nuisance tripping on capacitor-switching or motor-start transients while still meeting IEC 60947-2 Category A coordination requirements.

Panel integration

Single-pole width is 18 mm (2 x 9 mm pitches), so it occupies one module position in a distribution board. Tunnel-type terminals accept 1.5 to 35 mm² flexible or rigid copper — no need for pin ferrules on the larger sizes, though 35 mm² stranded benefits from a ferrule to avoid splaying under the screw. IP20 finger-safe terminals only — this is for enclosed panels, not open-wall mounting.

Approvals and documentation

Certified to EN/IEC 60947-2, pollution degree 3, suitability for isolation marked on the device. The toggle provides local ON/OFF indication with a contact position indicator that shows true contact state, not just handle position — a safety requirement for isolation switching. The C60N family carries CE and UKCA marking for European markets; separate earth-leakage protection block available as an add-on. RoHS and REACH compliance declarations are standard from Schneider Electric for this production code.

MPN