MGN61800 Multi9 C60H-DC MCB, 1P 6A Curve B DC

MPN MGN61800
Obsolete

Schneider Multi9 C60H-DC miniature circuit breaker, MGN61800, 1-pole 6 A curve B, 20 kA breaking at 110 V DC, DIN-rail clip-on.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61800 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 110 V DC 220 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61800 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated miniature breaker, 1-pole 6 A curve B

The MGN61800 is a Schneider Multi9 C60H-DC miniature circuit breaker — a 1-pole, 6 A unit with a B tripping curve, built specifically for DC networks. The key spec for a DC breaker is the breaking capacity: this one handles 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC per EN/IEC 60947-2.

Rated 6 A at 50 °C (thermal-magnetic trip), with a magnetic tripping threshold of 5.5 x In ±20 % DC. The 1-pole version protects one DC line; for a two-wire DC system (positive and negative), you'd use two units ganged together. The enclosure carries IP20 (finger-safe) and IP40 inside a modular enclosure.

Integration notes

Clip-on DIN-rail mount, 18 mm wide (2 modules). Strip length 14 mm, torque to 2.5 N·m. Padlockable toggle for lockout/tagout — the ON/OFF indicator shows contact position directly. Tropicalisation class 2 per IEC 60068-2 means it's treated against humidity and mold growth — relevant for outdoor cabinets or tropical climates.