Skip to main content
Schneider Electric MGN61840

Schneider Electric MGN61840 Multi9 C60H-DC MCB, 63 A, 1P, C

MPN MGN61840
Obsolete

Schneider Electric Multi9 C60H-DC, miniature circuit-breaker, MGN61840, 1P, 63 A, C curve, 20 kA Icu at 110 V DC, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61840 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 110 V DC 220 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN 60947-2

All specifications

MGN61840 additional specifications
ParameterValue
ColorGrey
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric MGN61840 is a Multi9 C60H-DC miniature circuit-breaker rated 63 A at 50 °C, single pole, with a C trip curve and a breaking capacity of 20 kA Icu at 110 V DC per EN/IEC 60947-2. It is designed for DC network distribution and clips onto a DIN rail for panel integration.

The C curve (magnetic tripping limit 8.5 x In ±20 % DC) means it tolerates moderate inrush currents — suitable for motor and transformer loads on DC circuits, not for purely resistive loads where a B curve would be tighter. Breaking capacity of 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC tells you the maximum fault current the breaker can safely interrupt at each voltage. For a 110 V DC bus, this handles most panel-level faults without cascading upstream. The rated insulation voltage of 500 V DC and operational voltage up to 250 V DC confirm it is built for DC rail voltages common in telecom, solar combiner boxes, and industrial control panels. Thermal-magnetic trip technology combines a bimetal strip for overload protection and a solenoid for short-circuit response. The 8.5 x In magnetic threshold on DC means the breaker holds through starting surges up to roughly 535 A before instant tripping — critical for DC motor drives or capacitor bank charging.

Deployment context

Clip-on mounting to DIN rail (35 mm per EN 60715) with a width of 18 mm (2 x 9 mm pitches) means it occupies a single modular slot in a distribution board. The IP20 finger-safe enclosure and IP40 modular enclosure rating allow installation in standard electrical cabinets without additional shrouding. Tunnel-type terminals accept up to 35 mm² rigid stranded cable (AWG 2) or 25 mm² flexible, with a tightening torque of 3.5 N.m. The breaker is padlockable for lockout/tagout procedures and provides ON/OFF local signalling with a contact position indicator.

MPN