Skip to main content
Schneider Electric MGP36450

MGP36450 PowerPact M Circuit Breaker, 450 A, 3P, ET 1.0

MPN MGP36450
Active

Square D PowerPact M, MGP36450, 3-pole unit mount circuit breaker, 450 A, ET 1.0 electronic trip, 65 kA at 240 V AC, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGP36450 key specifications
ParameterValue
Control typeOperating handle
Trip unit typeElectronic, basic, ET 1.0
Main product or component typeCircuit breaker
Voltage600 V AC 50/60 Hz UL 489
Insulation voltage ui750 V IEC 60947-2
Poles3P
IP ratingIP40
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-58...185 °F (-50...85 °C)

All specifications

MGP36450 additional specifications
ParameterValue
Pollution degree3 IEC 60947-1
ColorBlack
Depth8.05 in (204.47 mm)
Width8.27 in (210.06 mm)
Height12.86 in (326.64 mm)
AWG gauge3 x AWG 3/0...3 x 500 kcmil aluminium/copper
ApplicationDistribution
Operating temperature-13...158 °F (-25...70 °C)

Product details

The Square D MGP36450 is a PowerPact M unit mount circuit breaker, rated 450 A continuous at 80 % of the frame, with an ET 1.0 electronic trip unit. Three-pole, Category A utilisation, it's built for distribution duty — think main or feeder breaker in a panelboard or switchboard, not motor starting. The 65 kA AIR at 240 V AC (UL 489) means it can clear a bolted fault up to that level without rupturing; at 480 V AC that drops to 35 kA, and at 600 V AC to 18 kA. IEC 60947-2 Icu ratings run 50 kA at 240 V and 35 kA at 380/415 V. The ET 1.0 is a basic electronic trip — fixed magnetic pickup at 900 to 4500 A, no field-adjustable long-time or short-time bands. You get what the factory set, which keeps the BOM simple but limits coordination flexibility downstream.

Unit mount with lug terminations — line and load lugs accept 3 x AWG 3/0 up to 3 x 500 kcmil aluminium or copper. Tightening torque is 442.5 lbf·in (50 N·m) on the terminal nuts. The lug kit is AL800M23K. Stripping length is 1.0 in (25 mm). Operating altitude is 2000 m without derating, up to 4000 m with derating.

Current production — no end-of-life notice. UL 489, CSA, NEMA, NOM-003-SCFI-2000, and IEC 60947-2 approvals. CE marked. HACR rated. Auxiliary switch slot accepts two OF plug-in modules; one alarm switch SD plug-in; one voltage release MN or MX plug-in.

MPN
MGP36450