Schneider NG125L Circuit Breaker, 32 A 4-Pole, 690 V

MPN NG125L

Schneider Electric NG125L, 4-pole circuit breaker, 32 A at 40 °C, 690 V AC insulation, 8 kV impulse withstand, DIN-rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

NG125L specifications
ParameterValue
Product typeCircuit Breaker
Insulation voltage ui690 V AC 50/60 Hz
Current32 A at 40 °C
IP ratingIP20
Temp operating max70 °C
Temp operating min-30 °C
Weight0.99 kg
Electrical life cycles10000 cycles

Product details

That 40 °C reference point matters: if your panel runs warmer — say 50 °C — you need to derate the continuous current, or the bimetal trips early on a load that should hold. The 690 V AC insulation voltage (Ui) and 8 kV impulse withstand (Uimp) place it squarely in industrial distribution, not residential final circuits.

Tunnel terminals accept 1.5…50 mm² rigid copper; strip 20 mm and torque to 3.5 N·m. At 108 mm wide for four poles, it fills about six modular spaces on the rail — plan your gland-plate fill accordingly.

Electrical durability and frequency range

Rated for 10,000 electrical cycles — adequate for a distribution feeder or motor branch circuit that sees a few operations per day. Network frequency covers 50…60 Hz, so it works on both 50 Hz European and 60 Hz North American grids without derating.

MPN