Skip to main content
Schneider Electric RM4LG01B

Schneider RM4LG01B Liquid Level Control Relay, 22.5 mm

MPN RM4LG01B
Active

Schneider Electric Harmony RM4LG01B liquid level control relay, 22.5 mm width, 1 C/O output, sensitivity scale 5-100 kOhm, screw terminals, IP20 terminals / IP50 casing.

$232.77 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

RM4LG01B specifications
ParameterValue
TypeLiquid level control relay
Insulation voltage ui500 V IEC
IP ratingIP20 / IP50
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max65 °C
Temp operating min-20 °C
Storage temperature-40...185 °F (-40...85 °C)
Pollution degree3 IEC 60664-1
Width0.9 in (22.5 mm)
Mechanical life cycles30000000 cycles
Operating positionAny position without derating
Operating temperature-4...149 °F (-20...65 °C)

Product details

22.5 mm DIN-rail fit for level sensing

The RM4LG01B is a liquid level control relay from the Schneider Harmony RM4-L series, occupying 2.5 pitches of 9 mm on a DIN rail — that's a 22.5 mm footprint, so it slots into a standard panel without crowding adjacent control relays or terminal blocks. It detects liquid level through resistive probes, with a sensitivity scale adjustable from 5 to 100 kOhm, covering most conductive liquids from demineralised water to process chemicals.

Output and switching specs for pump control

A single changeover (1 C/O) contact with 90/10 silver-nickel alloy switches up to 250 V AC at 10 mA minimum, and the maximum switching voltage is 440 V AC. The 1.9 VA AC coil draw is light enough that a 24 V control transformer can drive several of these without derating. The electrode circuit is limited to 1 mA at 24 V AC — that's intentionally low to avoid electrolytic corrosion of the probe tips in conductive liquids.

Lifecycle and compliance for BOM planning

Pollution degree 3 per IEC 60664-1 and overvoltage category III mean it's rated for fixed industrial installations where transient overvoltages from the mains supply are expected — typical for a panel-mounted level relay.