Skip to main content
Schneider Electric VW3A46105

Schneider VW3A46105 Passive Filter, 30A, 400V, 50Hz, THDI 10

MPN VW3A46105
Active

Schneider Electric, Altivar series, passive filter, VW3A46105, 30 A rated, 400 V, 50 Hz, THDI 10 % for ATV630/ATV930/ATV650/ATV61W/ATV950 drives at 15 kW/20 hp.

$4,140.43 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

VW3A46105 specifications
ParameterValue
Main product or component typePassive filter
IP ratingIP20 / IP55
Temp storage max65 °C
Temp storage min-25 °C
Temp operating max60 °C
Temp operating min5 °C
Cos phi1 (150 % of line current) 0.85 (75 % of line current) 0.99 (100 % of line current)
Efficiency98%
Operating temperature45...60 °C (with current derating 3 % per °C) 5...45 °C (without current derating)

Product details

Harmonic mitigation for Altivar drives

The VW3A46105 is a passive filter designed to reduce current harmonics on the line side of Schneider Altivar variable speed drives. It targets the 15 kW / 20 hp frame across the ATV61, ATV71, ATV630, ATV650, ATV930, and ATV950 families — one filter per drive, per the specification. The THDI figure lands at 10 % for the ATV630, ATV650, ATV930, ATV950, and ATV61W platforms, and 16 % for the ATV61H, ATV71H, and ATV71W variants, all at the same motor rating. That difference matters for site compliance: a 10 % THDI keeps you inside IEC 61000-3-4 and G5/4 limits for most installations without additional line reactors.

Rated at 29 A input and 30 A output on a 400 V ±10 % three-phase supply at 50 Hz ±2 %. The 1 A delta between input and output accounts for the filter's own magnetizing current — expect to size upstream protection for the 29 A figure, not the output side. Power factor correction is load-dependent: cos φ reaches 1.0 at 150 % of line current, 0.99 at 100 %, and 0.85 at 75 %. That means the filter delivers near-unity PF across the normal operating band, but the PF drops if the drive is running well below its rated current. Thermal losses are 224 W at full load — factor that into enclosure cooling, especially in a sealed IP55 cabinet.

Environmental limits and derating

Operates without derating from 5 °C to 45 °C ambient. Above that, derate 3 % per °C up to 60 °C — a 50 °C ambient knocks the effective current rating down by 15 %, so size the drive/filter pair accordingly if the panel runs hot. Altitude derating kicks in above 1000 m at 5 % per 1000 m. The filter carries IP20 as standard, but the spec also lists IP55 for enclosure mounting — that's the panel's rating, not the filter's standalone ingress protection. Vibration resistance per IEC 60068-2-6: 2 mm peak-to-peak from 5 to 13.2 Hz, then 0.7 gn up to 150 Hz. Accepts 0.5 to 10 mm² on the main power terminals and 2.5 mm² on the control terminals.

MPN