Skip to main content
Schneider Electric A9DR3720

Schneider Electric A9DR3720 Acti9 iCV40 XA RCBO, 20 A C-curv

MPN A9DR3720
Obsolete

Schneider Electric Acti9 iCV40 XA RCBO, A9DR3720, 3P+N, 20 A, C-curve, 30 mA earth-leakage, 6 kA at 400 V AC, thermal-magnetic, DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9DR3720 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Voltage400 V AC 50/60 Hz
Insulation voltage ui440 V AC 50/60 Hz
Breaking capacity6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Terminal pitch18 mm between phases 9 mm between phase and neutral
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3

All specifications

A9DR3720 additional specifications
ParameterValue
ColorWhite
Depth73 mm
Width90 mm
Height93 mm
Electrical life cycles20000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The Schneider Electric A9DR3720 is an Acti9 iCV40 XA combined RCBO — a single module that packs a 20 A C-curve MCB and a 30 mA residual-current device into a 3P+N, 4-pole package. The thermal-magnetic trip handles overloads and short-circuits; the integrated RCD covers the 30 mA sensitivity for personnel protection.

The 30 mA earth-leakage sensitivity is the standard for socket-outlet and personnel protection circuits.

The 3P+N unit occupies 10 modules at 9 mm pitch (90 mm total width). Neutral is on the left. Connection pitch is 18 mm between phases, 9 mm between phase and neutral. Wire stripping length is 14 mm for the bottom connection. IP20 body, IP40 inside the modular enclosure — fine for a dry indoor distribution board, not for washdown areas.

MPN
A9DR3720