Schneider Electric A9F07163

Schneider A9F07163 Acti9 iC60H MCB, 63 A C-Curve, 1P

MPN A9F07163
Active

Schneider Electric Acti9 iC60H, 63 A, C-curve, 1-pole miniature circuit-breaker, 42 kA Icu at 12-60 V AC, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F07163 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C

All specifications

A9F07163 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width18 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The Schneider A9F07163 is a 63 A, 1-pole miniature circuit-breaker from the Acti9 iC60H series, designed for distribution board duty. At 230 V AC the Icn is 10,000 A per EN/IEC 60898-1, which is the standard domestic/commercial rating; the higher Icu figures per EN/IEC 60947-2 cover the industrial fault levels. Dual-certified to both standards, so it fits either a residential load center or an industrial sub-panel.

Height 91 mm, depth 78.5 mm. Strip length 14 mm. Toggle actuator with a visible trip indicator; the contact position indicator confirms isolation visually.

Current-production part — no end-of-life notice issued. The Acti9 iC60 family is Schneider's mainstream MCB line, widely specified across European and Middle Eastern panels.

What the approvals tell you

Dual-listed to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/commercial). Isolation-suitable per both standards. Overvoltage category IV — rated for the main incomer, not just downstream sub-circuits.

MPN
A9F07163