Skip to main content
Schneider Electric A9F43401

A9F43401 iC60N MCB, 1A 4P B-Curve, 50 kA Icu, Acti9

MPN A9F43401
Obsolete

Schneider Electric Acti9 iC60N, A9F43401, miniature circuit breaker, 1 A rated, 4 poles, B curve, 50 kA Icu at 415 V AC, clip-on rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F43401 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 250 V DC
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C
Storage temperature-40...85 °C

All specifications

A9F43401 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width72 mm
Height85 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
Operating temperature-35...70 °C

Product details

The Schneider Electric A9F43401 is an iC60N miniature circuit breaker from the Acti9 range, rated 1 A with 4 protected poles and a B tripping curve. It carries a 50 kA Icu breaking capacity at 415 V AC per EN/IEC 60947-2, and 6 kA Icn per EN/IEC 60898-1 — dual-rated so it fits both residential distribution boards and industrial panel schedules. The thermal-magnetic trip unit triggers magnetically at 4 x In (±20 %), which for a 1 A breaker means instant trip above roughly 4.8 A; the B curve is standard for resistive or light inductive loads where you want fast short-circuit clearance without nuisance tripping on inrush.

Breaking capacity and dual standard

Rated Icu of 50 kA at 415 V AC under EN/IEC 60947-2 means this breaker can safely interrupt a 50 kA prospective fault current without welding its contacts — that is industrial-grade fault clearance for a 1 A device, usually found in sub-distribution boards fed by a large transformer. The limitation class is 3 per EN/IEC 60898-1, meaning it limits let-through energy well enough to protect downstream equipment in a coordinated system.

Clip-on mounting onto a standard DIN rail, 9 mm pitch occupies 8 modules (72 mm wide). The 4-pole format with a toggle control and a trip indicator gives visual confirmation of the tripped pole.

MPN
A9F43401