Skip to main content
Schneider Electric A9F44370

Schneider Electric A9F44370 Acti9 iC60N MCB, C-Curve 0.5A 3P

MPN A9F44370
Obsolete

Schneider Electric Acti9 iC60N, miniature circuit breaker, 0.5 A, C-curve, 3P, 50 kA Icu at 415 V AC, clip-on DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F44370 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 180 V DC
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C

All specifications

A9F44370 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width54 mm
Height85 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
Operating temperature-35...70 °C

Product details

The Schneider Electric A9F44370 is an Acti9 iC60N miniature circuit breaker — a 3-pole, 0.5 A rated, C-curve device built to protect branch circuits in commercial and industrial panels. The 0.5 A rating is the continuous current it carries without tripping; the C-curve means its magnetic trip activates at 5 to 10 times rated current (8 x In ±20% here), so it handles moderate inrush from small transformers or control loads without nuisance tripping.

DIN-rail fit and wiring details

The 54 mm width (6 x 9 mm pitches) occupies three standard modular slots on the rail. Depth is 78.5 mm, height 85 mm — check gland-plate clearance if the panel is shallow. Terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible; strip length is 14 mm. The thermal-magnetic trip unit gives 10,000 electrical cycles and 20,000 mechanical cycles — fine for a distribution board that sees infrequent switching. The trip indicator and contact position indicator give visual confirmation of state without needing a multimeter.

Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household / similar) — that covers both the high breaking capacity (60947-2) and the standard MCB coordination (60898-1). Earth-leakage protection is handled by a separate block (not built-in).

MPN
A9F44370