Skip to main content
Schneider Electric A9F45401

Schneider Electric A9F45401 Acti9 iC60N MCB, 1 A D Curve, 4P

MPN A9F45401
Obsolete

Schneider Electric Acti9 iC60N, miniature circuit breaker, 4P, 1 A, D curve, 50 kA breaking capacity, clip-on rail mounting, white.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F45401 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 250 V DC
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C
Storage temperature-40...85 °C

All specifications

A9F45401 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width72 mm
Height85 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
Operating temperature-35...70 °C

Product details

What this 1 A D-curve MCB is for

The Schneider Electric A9F45401 is a 4-pole Acti9 iC60N miniature circuit breaker rated at 1 A with a D tripping curve. The D curve's magnetic trip threshold of 12 x In (±20 %) means it takes a sustained 12 A fault to trigger the instantaneous magnetic release; below that, the thermal-magnetic trip handles overloads. That 1 A rating makes it a fit for control transformers, relay coils, or PLC power supplies pulling under an amp per phase. The 4-pole version protects all four conductors in a three-phase-plus-neutral circuit. At 72 mm wide, it takes up eight 9 mm pitch modules on the rail, so plan your enclosure fill factor accordingly.

Breaking capacity and dual-standard rating

This breaker carries dual certification to EN/IEC 60898-1 (the household-and-similar MCB standard) and EN/IEC 60947-2 (the industrial circuit-breaker standard). That matters for panel builders who need one part number that satisfies both a residential-style distribution board and an industrial switchboard. The industrial rating gives a 50 kA Icu at 220...240 V AC and 380...415 V AC, dropping to 25 kA at 440 V AC. For most motor-control panels fed from a 400 V transformer, the 50 kA Icu is the number that governs the upstream fault level. Overvoltage category IV covers the main incoming supply side, so it's suitable as a service-entrance or main-distribution breaker, not just downstream sub-feed.

The connection is a single terminal per pole (top and bottom), so you land one conductor per side — no looping through the breaker. The toggle control with trip indicator gives local visual confirmation of the tripped state.

Environmental and durability ratings

IP20 finger protection per IEC 60529 — fine for enclosed panels, not for wet locations. Padlockable for lockout/tagout procedures.

MPN