Skip to main content
Schneider Electric A9N1P03DGN

Schneider Electric A9N1P03DGN Acti9 xC60 MCB, 3A D Curve, 10

MPN A9N1P03DGN
Active

Schneider Electric Acti9 xC60 miniature circuit-breaker, A9N1P03DGN, 1P, 3 A rated, D curve, 10 kA Icn at 240 V AC, clip-on 35 mm DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9N1P03DGN key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage220...240 V AC 50/60 Hz
Breaking capacity10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...85 °C
Pollution degree3

All specifications

A9N1P03DGN additional specifications
ParameterValue
ColorWhite
Depth77.5 mm
Width18 mm
Height85 mm
Electrical life cycles20000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

What this MCB does on the panel

The Schneider Electric A9N1P03DGN is a 1-pole Acti9 xC60 miniature circuit-breaker rated 3 A with a D tripping curve. Breaking capacity is 10,000 A Icn at 240 V AC, 50/60 Hz, certified to IS/IEC 60898-1.

D curve — why it matters for your load

The D curve is the distinguishing spec on this 3 A MCB. Where a B curve trips magnetically at 3–5× In and a C curve at 5–10× In, the D curve holds until 10–14× In. That means a 3 A D-curve breaker will pass a 30–42 A inrush pulse without opening — exactly what you need when the load is a small motor starting direct-on-line, a solenoid bank pulling in, or a power supply charging its bulk capacitors. If the branch feeds resistive or general-purpose loads, a C curve would be the standard choice; the D curve here is deliberately selected for inductive or high-inrush circuits.

The toggle actuator gives local ON/OFF indication. IP20 finger-safe protection means it's suitable for enclosed panels only — no exposed live parts when installed in a proper enclosure.

MPN
A9N1P03DGN