Skip to main content
Schneider Electric ATV1200A11904242

Schneider Electric ATV1200A11904242 AC Drive, 995 kW

MPN ATV1200A11904242
Obsolete

Schneider Electric Altivar 1200 series, ATV1200A11904242 AC Drive (VFD) 480V, 995 kW motor power, 1190 kVA apparent power, 24-pulse diode rectifier, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A11904242 specifications
ParameterValue
Input type24 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current200 A
IP ratingIP41 / IP31 / IP42
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1400 mm (standard efficiency) 1600 mm (high efficiency)
Width4060 mm (standard efficiency) 4360 mm (high efficiency)
Height2670 mm high efficiency 2670 mm standard efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

Medium-voltage drive for large motor loads

The ATV1200A11904242 is a medium-voltage AC drive from the Altivar 1200 series, rated for 995 kW motor power with 1190 kVA apparent power. It accepts a 2970...3630 V supply via a 24-pulse diode rectifier bridge, which inherently cancels the 5th and 7th harmonics — a practical advantage for plants with strict IEEE 519 compliance targets or weak utility connections. The drive supports both synchronous and asynchronous motors, with overload capability of 1.2 In for 60 s (standard) or 1.5 In for 60 s (high overload). This matters for applications like large conveyors or mills that need breakaway torque without oversizing the drive frame.

Physical footprint and site preparation

This is a floor-standing enclosure, not a panel-mount unit. Standard-efficiency configuration measures 4060 mm wide × 1400 mm deep × 2670 mm high; the high-efficiency variant adds width to 4360 mm and depth to 1600 mm. Site planning must account for the 16500 m³/h (standard) or 19900 m³/h (high-efficiency) cooling airflow — forced convection with separate air paths for power and control sections. The enclosure colour is grey (RAL 7032). Electrical connection uses M10 screw-type bars accepting up to 6 × 40 mm² per phase, entry from top or bottom. Operating position is vertical within ±10 degrees.

Power architecture and cell topology

The ATV1200A11904242 uses a multi-cell topology: 12 power cells fed by a phase-shifting transformer with two plinths. Each cell is a modular inverter stage; the 24-pulse input rectifier keeps line current distortion low without external filters. The integrated EMC filter meets EN/IEC 61800-3 conducted emissions limits for the intended industrial environment. Prospective short-circuit current withstand is 31.5 kA for 150 ms — sufficient for most industrial distribution systems when properly coordinated upstream.

Control interfaces and I/O complement

The drive carries 4 software-configurable analogue inputs (0...20 mA / 4...20 mA, 24 V max, 250 Ohm impedance) and 2 analogue outputs of the same type. Discrete inputs number 6 standard, expandable to 10. The human-machine interface is included as standard equipment. Control supply requires 220 V AC at 3 kVA (external), with an optional 220 V AC/DC supply. The cooling fan runs on 380 V AC internal supply, also available as an external option. Electrical isolation between power and control circuits is standard.

Environmental limits and derating

Operating altitude range is 1000...2000 m with current derating of 0.6 % per 100 m above 1000 m. Relative humidity tolerance is 0...90 % standard, 0...95 % optional. Vibration resistance is 4.9 m/s² over 10...50 Hz. Noise level at full load is 80 dB — factor this into enclosure room acoustic planning. Speed range is 20:1 to 100:1, adequate for centrifugal loads (pumps, fans) and constant-torque applications (conveyors, extruders) within the motor's thermal capability at low speed.

Lifecycle status and sourcing

CE marking is standard. Standards compliance includes EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3 (EMC), EN/IEC 61800-4, and EN/IEC 61800-5-1 (safety). Ground fault protection is integrated at the drive level.

MPN
ATV1200A11904242