Skip to main content
Schneider Electric ATV1200A37606363

Schneider Electric ATV1200A37606363 Altivar 1200, 2918 kW

MPN ATV1200A37606363
Active

Schneider Electric Altivar 1200 ATV1200A37606363, medium-voltage AC drive, 2918 kW motor power, 3490 kVA apparent power, 36-pulse diode rectifier, floor-standing enclosure, CE.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A37606363 specifications
ParameterValue
Input type36 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current320 A
IP ratingIP31 / IP41 / IP42
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1700 mm (high efficiency) 1700 mm (standard efficiency)
Width6670 mm (standard efficiency) 6670 mm (high efficiency)
Height2670 mm standard efficiency 2970 mm high efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

2918 kW, 3490 kVA — medium-voltage mill drive

The ATV1200A37606363: Rated motor power of 2918 kW with an apparent power of 3490 kVA and line current of 320 A. The supply voltage limits span 2970–3630 V — this is a medium-voltage drive, not a 480 V class unit, so the incoming transformer and switchgear must be rated for the 3 kV class. The 36-pulse diode rectifier front end delivers inherently low line-current harmonic distortion without an active front end or external filter bank. For a hot-strip mill or large pump/fan installation, this simplifies harmonic compliance studies and avoids the cost of a multi-pulse transformer.

Overload profile and duty cycle

Standard overload rating: 1.2 × rated current for 60 seconds, 1.5 × for 3 seconds. High-overload rating: 1.5 × for 60 seconds, 1.85 × for 3 seconds. The high-overload curve suits applications with intermittent peak torque demands — crushers, mixers, or mill table drives where the load spikes during breakaway. The drive handles both synchronous and asynchronous motors, so it can replace an older DC drive on a mill stand or drive a new synchronous motor for a high-efficiency retrofit.

Physical footprint and facility planning

Floor-standing enclosure with separate air flows for the transformer and power cells. Standard-efficiency configuration: 6670 mm wide × 1700 mm deep × 2670 mm high. High-efficiency configuration: same footprint but 2970 mm tall. The 80 dB noise level means hearing protection zones around the drive cabinet are mandatory. Cooling air volume is 33,000 m³/h for both efficiency variants. The forced-convection cooling system requires a dedicated HVAC supply sized for that airflow — not a trivial plant engineering detail. Operating position is vertical ±10 degrees.

Standards and isolation

CE marked. Designed to EN/IEC 61800-3 (EMC), EN/IEC 61800-4 (harmonics), EN/IEC 61800-5-1 (safety), EN/IEC 60204-11 (machinery), and EN/IEC 60529 (enclosure protection). Pollution degree 2 per EN/IEC 61800-5-1 — typical for controlled electrical rooms, but not for dusty mill environments without supplementary cabinet filtration. Electrical isolation between power and control circuits. Dielectric strength tested at 20 kV AC between earth and power terminals — confirms the medium-voltage isolation barrier is intact for the 3 kV class supply. Prospective line short-circuit current rated at 31.5 kA for 150 ms. Overvoltage category II per EN/IEC 61800-5-1.

Altitude and environment derating

Standard operating altitude is 1000 m. Above that, derate output current by 0.6 % per 100 m up to 2000 m. For a mill at 1500 m elevation, the effective current capability drops by 3 % — factor this into the motor sizing if the drive is already at the overload limit. Relative humidity range 0–90 % standard, 0–95 % optional. The drive includes ground fault protection and an integrated EMC filter.

I/O complement and control wiring

Four software-configurable analogue inputs (0–20 mA / 4–20 mA, 24 V max, 250 Ω impedance). One analogue output of the same type. Six discrete inputs standard, expandable to ten. The 220 V AC control supply requires a 3 kVA external transformer — not included in the drive cabinet. Main power connection via M10 screw-type bar terminals accepting 6 × 40 mm² cable, entry from bottom or top. The internal cooling fan supply is 380 V AC; an optional external 220 V AC/DC control supply is available.

MPN
ATV1200A37606363