Schneider Electric ATV1200A50001010

Schneider ATV1200A50001010 AC Drive, 4180 kW, 5000 kVA

MPN ATV1200A50001010
Active

Schneider Electric Altivar 1200 ATV1200A50001010 medium-voltage AC drive, 4180 kW motor power, 5000 kVA apparent power, 48-pulse diode rectifier input, 2970...3630 V supply, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A50001010 specifications
ParameterValue
Input type48 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current320 A
IP ratingIP42 / IP41 / IP31
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1600 mm (standard efficiency)
Width9070 mm (standard efficiency)
Height3040 mm standard efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

Rated 4180 kW motor power at 5000 kVA apparent power, the ATV1200A50001010 is sized for large asynchronous motor loads — pumps, compressors, fans, and conveyors in the 4 MW class. The 48-pulse diode rectifier bridge on the input side keeps line-side harmonics low enough to meet IEEE 519 without a separate filter in most installations. Supply voltage range is 2970...3630 V — this is a medium-voltage drive, not a 480 V unit. The output voltage tracks the supply voltage, so the motor winding insulation and cable rating must match the incoming line voltage. Overload capability is defined in four profiles: 1.2× In for 60 s and 1.5× In for 3 s under standard overload, plus 1.5× In for 60 s and 1.85× In for 3 s under high overload. The high-overload profile supports starting high-inertia loads or clearing short-duration process peaks without oversizing the drive.

Floor-standing enclosure and cooling — installation constraints

The drive ships in a floor-standing enclosure measuring 1600 mm deep by 9070 mm wide by 3040 mm high. That footprint requires a dedicated equipment room with front and rear access for cable entry and maintenance. The enclosure has separate air flows for the power section and control compartment, with forced-convection cooling moving 56400 m³/h of air. Power connections are bar-type M10 screw terminals accepting up to 6 × 40 mm² per phase, with cable entry from the top or bottom. The main power cell assembly includes 24 individual power cells, a phase-shifting transformer, medium-voltage arrestors, and cooling fans — all field-replaceable subassemblies. Operating position is vertical within ±10 degrees. Altitude derating starts at 1000 m: 0.6 % current derating per 100 m above that. Ambient relative humidity range is 0...90 % (0...95 % optional).

Standards compliance and protection — what the certifications cover

The drive carries CE marking and complies with EN/IEC 60204-11 (electrical equipment of machines), EN/IEC 60529 (enclosure protection), EN/IEC 61800-3 (EMC for adjustable-speed drives), EN/IEC 61800-4 (drive system requirements), and EN/IEC 61800-5-1 (electrical, thermal, and energy safety). The integrated EMC filter covers conducted emissions for industrial environments. Electrical isolation between power and control circuits is maintained. Dielectric strength is 28 kV AC between earth and power terminals. Overvoltage category II per EN/IEC 61800-5-1, pollution degree 2. Prospective line short-circuit current withstand is 31.5 kA for 150 ms. Ground fault protection is built into the drive. Noise level at full load is 80 dB — hearing protection is required within the equipment room during operation.

Control interface and I/O complement

The control section has 4 software-configurable analogue inputs (0...20 mA / 4...20 mA, 24 V max, 250 Ohm impedance) and 1 analogue output (0...20 mA / 4...20 mA DC, 250 Ohm impedance). Discrete inputs: 6 standard, expandable to 10 with the optional card. Control power supply is 220 V AC, 3 kVA, with an optional 220 V AC/DC external supply. The cooling fan supply is 380 V AC, also with an optional external feed. The human-machine interface is included as part of the standard product composition.

Sourcing and lifecycle — active production, quoted to order

The drive is supplied as a complete floor-standing assembly including the phase-shifting transformer, power cells, cooling fans, HMI, and medium-voltage arrestors. Spare subassemblies (power cells, fan modules, control boards) are available separately through the same sourcing channel.

MPN