Skip to main content
Schneider Electric ATV1200A56006666

Schneider ATV1200A56006666 Altivar 1200 VFD, 4682 kW, 3.3 kV

MPN ATV1200A56006666
Active

Schneider Electric Altivar 1200 ATV1200A56006666 medium-voltage variable speed drive, 4682 kW, 2970-3630 V supply, 36-pulse diode rectifier, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A56006666 specifications
ParameterValue
Input type36 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current490 A
IP ratingIP31 / IP42 / IP41
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1800 mm (standard efficiency) 1800 mm (high efficiency)
Width6670 mm (standard efficiency) 6970 mm (high efficiency)
Height2820 mm standard efficiency 3040 mm high efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

4682 kW medium-voltage drive for large asynchronous motors

The ATV1200A56006666 is a Schneider Electric Altivar 1200 medium-voltage variable speed drive rated for 4682 kW motor output. It accepts a 2970-3630 V supply via a 36-pulse diode rectifier bridge, which significantly reduces line harmonics compared to 12- or 18-pulse topologies. It is designed for large asynchronous motors in heavy industrial applications — think pumps, fans, compressors, and conveyors in mining, cement, water, and oil & gas where medium-voltage direct drive is needed.

Overload profile and cooling — what the ratings mean

The drive delivers standard overload of 1.2 In for 60 s and 1.5 In for 3 s; for high-overload duty it handles 1.5 In for 60 s and 1.85 In for 3 s. This means it can handle short-duration peak torque demands typical of crushers or centrifuge starts without tripping. Forced convection cooling moves 80,000 m³/h of air through the floor-standing enclosure, with separate airflows for power and control sections. The noise level is 80 dB — factor in hearing protection if the drive is in a walk-in room.

Physical footprint and installation constraints

The standard-efficiency variant measures 1800 mm deep, 6670 mm wide, and 2820 mm high. The high-efficiency version is wider at 6970 mm and taller at 3040 mm. Both require vertical installation within ±10° and a floor-standing enclosure with separate air flows. Operating altitude from 1000 to 2000 m requires current derating of 0.6 % per 100 m. Pollution degree 2 per EN/IEC 61800-5-1 applies, meaning only non-conductive pollution occurs — typical for clean indoor industrial environments.

MPN
ATV1200A56006666