Skip to main content
Schneider Electric C160N420FM

C160N420FM ComPacT NS 1600A 4P Circuit Breaker, MicroLogic 2

MPN C160N420FM
Active

Schneider Electric ComPacT NS new generation, C160N420FM, 1600 A, 4-pole, fixed-mount circuit breaker with MicroLogic 2.0 electronic trip unit, 85 kA Icu at 240 V AC.

$3,302.96 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C160N420FM key specifications
ParameterValue
Control typeManually operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Utilization categoryCategory B
IP ratingIP40
Terminal pitch70 mm
Connection surface topFront
Connection surface bottomFront

All specifications

C160N420FM additional specifications
ParameterValue
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degree3 conforming to IEC 60947
Depth147 mm
Width280 mm
Height327 mm
Electrical life cycles1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

What this 1600 A breaker does for a distribution panel

The C160N420FM is a fixed-mount, 4-pole ComPacT NS new generation circuit breaker rated 1600 A at 50 °C, built for main or feeder distribution in commercial and industrial switchboards. The MicroLogic 2.0 electronic trip unit provides L (long-time overload) and I (instantaneous short-circuit) protection curves — no ground-fault module on this variant. Breaking capacity hits 85 kA Icu at 240 V AC and 50 kA Icu at 415 V AC, both per IEC 60947-2, so it handles high-fault utility feeds without cascading upstream. Front-connect terminals on a 70 mm pitch simplify busbar alignment in a fixed-backplate layout.

At 690 V AC the Icu drops to 30 kA — still enough for most industrial loads, but verify against the transformer impedance if you're feeding a 690 V bus. Category B utilisation means the breaker is designed for selectivity with downstream breakers; the short-time withstand (not explicitly listed here but implied by Cat B) allows delayed tripping on a fault so the downstream device clears first.

Lifecycle and sourcing — active production, no LTB watch needed

The C160N420FM carries a current lifecycle stage from the manufacturer — no phase-out notice, no last-time-buy window. This is a standard catalogue item in the ComPacT NS new generation family, which Schneider continues to develop and support.

Mounting and integration — fixed-backplate, front-connect

Fixed-mount on a backplate, not DIN-rail. The 280 mm width and 327 mm height need a cutout sized for the ComPacT NS630b–1600 footprint; the 70 mm connection pitch matches standard busbar drilling for 1600 A class. Front-connect terminals on both upside and downside keep cabling accessible in a row of fixed breakers. IP40 enclosure protection means it's suited for indoor switchboard cubicles — not washdown or outdoor without an additional enclosure. IK07 impact rating handles accidental tool strikes during panel assembly.

MPN
C160N420FM