Schneider Electric C25F44V160

Schneider C25F44V160 ComPacT NSX 160A MCCB, 85kA Icu

MPN C25F44V160
Obsolete

Schneider Electric ComPacT NSX, C25F44V160, 160 A MCCB, 4P, MicroLogic 4.2 electronic trip unit, 85 kA Icu at 240 V AC, 36 kA at 415 V AC, IP40, backplate mount.

$1,322.27 – $2,913.84 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25F44V160 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C25F44V160 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

160 A MCCB with MicroLogic 4.2 — distribution-grade protection for panel builders

The Schneider Electric C25F44V160 is a 4-pole ComPacT NSX250F molded-case circuit breaker rated 160 A at 40 °C, fitted with a MicroLogic 4.2 electronic trip unit. This makes it a single-device solution for both overcurrent and ground-fault protection in a distribution panelboard.

Breaking capacity across common voltage levels

The C25F44V160 delivers 85 kA Icu at 220/240 V AC, 36 kA at 380/415 V AC, 35 kA at 440 V, 30 kA at 500 V, 22 kA at 525 V, and 8 kA at 660/690 V AC, all per IEC 60947-2. Under UL 60947-4-1 it is rated 85 kA at 240 V, 35 kA at 480 V, and 15 kA at 600 V AC.

The 4-pole unit has neutral on the left. IP40 enclosure protection suits indoor panel installation; IK07 impact resistance handles typical cabinet handling.

Trip unit and protection characteristics

The MicroLogic 4.2 electronic trip unit includes thermal memory with a 20-minute retention before and after tripping — this prevents nuisance reclosure on a hot conductor. Local signalling includes a flashing green LED for ready-to-operate, red LED at 105 % Ir for overload, and orange LED at 90 % Ir for pre-alarm. The toggle control type provides manual on/off with the IΔn rotary switch for earth-leakage testing. Electrical durability is 20,000 cycles at 440 V In/2 and 10,000 cycles at 440 V In; mechanical durability is 20,000 cycles.

MPN