Skip to main content
Schneider Electric C63N34V570

Schneider Electric C63N34V570 ComPacT NSX630N, 570 A, 85 kA

MPN C63N34V570
Active

Schneider Electric, ComPacT NSX series, earth leakage circuit breaker, C63N34V570, 3P, 570 A at 40 °C, 85 kA Icu at 240 V AC, MicroLogic 4.3 trip unit.

$2,212.32 – $5,438.88 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C63N34V570 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C63N34V570 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth110 mm
Width140 mm
Height255 mm
Electrical life cycles8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Mechanical life cycles15000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

That 570 A is the continuous current the trip unit carries without tripping — sized for a main feeder or large downstream distribution board, not a branch circuit. The 85 kA Icu at 240 V AC (50/60 Hz) is the maximum fault current it can interrupt and still be usable afterward; at 480 V AC that drops to 50 kA Icu, and at 690 V AC to 10 kA Icu. For a 480 V panel with an available fault current of, say, 65 kA, this breaker clears it — but at 690 V you need the higher-rated frame. The MicroLogic 4.3 electronic trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection curves. The earth-leakage is integrated — no external Vigi module needed, which saves a pole width in the panel.

Deployment context

Backplate-mounted in a distribution panel, 140 mm wide × 255 mm high × 110 mm deep. IP40 enclosure protection means it's indoors only — no washdown or outdoor exposure without a secondary enclosure.

Overvoltage category IV, utilization category A. Breaking capacities also listed per UL 60947-4-1 at 240 V (85 kA), 480 V (50 kA), and 600 V (20 kA) — relevant for North American installations where UL listing is required.

MPN