Skip to main content
Schneider Electric LUCA12BTQ

Schneider LUCA12BTQ TeSys U Control Unit, 24 V AC, 5.5 kW

MPN LUCA12BTQ
Obsolete

Schneider Electric TeSys U standard control unit LUCA12BTQ, 24 V AC control voltage, for 3-phase motor protection up to 5.5 kW at 400 V, Class 10 thermal overload, plug-in front face.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LUCA12BTQ specifications
ParameterValue
Main product or component typeStandard control unit
Voltage690 V AC
Coil voltage24 V AC
Utilization categoryAC-44 AC-43 AC-41
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Depth60 mm
Width45 mm
Height66 mm
ApplicationMotor control Motor protection
Fixing modePlug-in (front face)
Operating temperature-25...70 °C

Product details

What this control unit does

The Schneider LUCA12BTQ is a standard control unit in the TeSys U motor starter range, designed for basic motor protection: overload, short-circuit, phase failure, and earth fault. It operates on a 24 V AC control circuit and is rated for motor power up to 5.5 kW at 400...440 V AC, 5.5 kW at 500 V AC, and 9 kW at 690 V AC.

Mounts via plug-in front face onto a TeSys U power base or contactor — no DIN-rail tool needed, just snap it in. Dimensions are 66 mm high, 45 mm wide, 60 mm deep, fitting the standard TeSys U footprint. IP20 on the front panel and wired terminals; IP40 on the front panel outside the connection zone. Control circuit voltage limits are 20...26.5 V AC for operation, with dropout at 14.5 V AC — so a saggy 24 V supply that dips below 20 V will drop the starter out, which matters if you're sharing a control transformer with other loads.

Protection and coordination

Tripping threshold is 14.2 x Ir ±20 %, giving a short-circuit trip fast enough to coordinate with most upstream MCCBs or fuses. Phase failure sensitivity is built in — no separate module needed. Immunity to microbreaks is 3 ms, so brief line sags won't cause nuisance dropouts. Safe separation of 400 V SELV between control/auxiliary and main circuits means you can share a 24 V control bus without worrying about creepage to line voltage.

MPN