Skip to main content
Schneider Electric MGN61868

MGN61868 Multi9 C60H-DC MCB, 20 A, 1P, Curve K, DC

MPN MGN61868
Obsolete

Schneider Electric Multi9 C60H-DC, miniature circuit-breaker, 1P, 20 A, curve K, 250 V DC, breaking capacity 20 kA at 110 V DC / 10 kA at 220 V DC / 6 kA at 250 V DC, clip-on DIN rail mount, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61868 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 110 V DC 220 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN 60947-2

All specifications

MGN61868 additional specifications
ParameterValue
ColorGrey
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric MGN61868 is a Multi9 C60H-DC miniature circuit-breaker — a 1-pole, thermal-magnetic unit rated 20 A at 50 °C, with a K-curve trip characteristic designed specifically for DC networks. The 73 mm depth keeps the breaker within typical enclosure clearances — no need to rework the gland plate or switch to a deeper box. The DC rating is the headline: it carries 20 A continuous and interrupts faults at 20 kA Icu at 110 V DC, 10 kA Icu at 220 V DC, and 6 kA Icu at 250 V DC, all per EN/IEC 60947-2. That means it can clear a dead short on a 220 V DC bus — common in solar combiner boxes, battery banks, and DC motor drives — without welding its contacts shut. The K curve (12 x In magnetic trip, +/-20%) is faster than a B or C curve on moderate overloads, which suits inductive DC loads like contactor coils and solenoids that draw a brief inrush.

Integration notes — DIN rail, terminals, and environment

Clip-on mounting to a standard DIN rail. Strip length is 14 mm; tighten to 2.5 N·m. Mechanical durability is 20,000 cycles; electrical durability is 3,000 cycles at L/R = 2 ms (typical for DC loads with some inductance).

MPN
MGN61868