Skip to main content
Schneider Electric CR1BM33M21

Schneider CR1BM33M21 TeSys F Bistable Contactor, 1000 A AC-3

MPN CR1BM33M21
Obsolete

Schneider Electric TeSys F CR1BM33M21, magnetic contactor, 3-pole, 1000 A AC-3, 1250 A Ith, bistable latching coil 220-230 V AC 50-400 Hz.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

CR1BM33M21 specifications
ParameterValue
Coil typeStandard
Main product or component typeMagnetic contactor
VoltagePower circuit: 1000 V AC Power circuit: 1000 V DC
Coil voltage220 V AC 50...400 Hz 230 V AC 50...400 Hz
Current1000 A (at 1250 A (at 800 A (at <40 °C) AC/DC AC-4 for power circuit
Temp operating max70 °C
Temp operating min-15 °C
Depth375 mm
Width475 mm
Height490 mm
Mechanical life cycles1000000 cycles
Operating time100...150 ms latching 20...40 ms unlatching
Operating position+/- 5°
Operating temperature-15...70 °C

Product details

The CR1BM33M21 is a TeSys F magnetic contactor from Schneider Electric, a bistable (latching) 3-pole device rated for 1000 A in AC-3 duty at 440 V — that's the motor-switching rating, so it handles heavy induction motor loads up to that current.

Coil and control circuit — the bistable latching logic

This is a latching contactor: the coil draws power only during the switching transition, then holds its state magnetically. Control voltage is 220-230 V AC, 50-400 Hz. Latching consumption hits 1100-1650 VA depending on frequency; unlatching is lower, 100-165 VA. The coil operates between 85% and 110% of rated voltage for both latching and unlatching. Operating time is 100-150 ms to latch, 20-40 ms to unlatch.

Breaking capacity and fault clearance

Rated breaking capacity varies with voltage: 10000 A at 220-440 V, 8000 A at 600-690 V, 4000 A at 1000 V. The making capacity (Irms) is 10000 A. For fault protection, the manufacturer specifies 1200 A aM, gG, or BS88 fuses on the power circuit. This gives the panel builder a clear coordination target for upstream protection.

Thermal performance and operating conditions

Power dissipation per pole is 280 W in AC-1 (resistive) and 180 W in AC-3 (motor) duty — relevant for enclosure heat rise calculations. Ambient operating range is -15 to 70 °C. Mechanical durability is rated at 1,000,000 cycles, with a maximum operating rate of 120 cycles per minute at 40 °C.

Insulation coordination and standards compliance

Rated insulation voltage (Ui) for the control circuit is 1000 V per BS 775, IEC 60158-1, and IEC 60947-4, and 1500 V per VDE 0110 group C. The power circuit is rated for 1000 V AC and 1000 V DC. The contactor carries protective treatment TH (tropicalized, humidity-resistant).

MPN