Skip to main content
Schneider Electric MGN25087

MGN25087 C60H MCB, 1P D-curve 20 A, 15 kA

MPN MGN25087
Obsolete

Schneider Electric Multi9 C60H series, MGN25087 miniature circuit breaker, 1-pole, D-curve, 20 A, 15 kA Icu at 240 V AC, thermal-magnetic trip, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN25087 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage240 V AC 50/60 Hz phase to neutral
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C
Pollution degree3 conforming to EN/IEC 60947-2

All specifications

MGN25087 additional specifications
ParameterValue
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The MGN25087 is a 1-pole C60H miniature circuit breaker from the Multi9 range, rated 20 A with a D tripping curve and a 15 kA Icu breaking capacity at 240 V AC. For a 415 V AC phase-to-neutral circuit, the Icu drops to 4 kA — that's the limit to respect when coordinating upstream. It's a thermal-magnetic breaker, so the thermal bimetal handles overloads and the solenoid handles short-circuits. The 1-pole form factor clips onto a 35 mm symmetrical DIN rail and occupies 2 x 9 mm pitches (18 mm wide) — standard for a single-pole MCB in a distribution board.

Where it fits — panel integration and compliance

The breaker is suitable for isolation — the toggle gives a visible ON/OFF indication and a contact position indicator so you can verify the circuit is open before working downstream. That's a practical check for maintenance techs isolating a motor branch circuit.

The part carries EN/IEC 60947-2 certification, which covers the breaking capacity and service duty for industrial and commercial distribution. That's the standard most panel builders and site electrical engineers will check for coordination studies. No UL or CSA listing is on the evidence for this specific code, so if your project requires those marks, verify before specifying.

What the D-curve means for selectivity

The D-curve's magnetic trip at 12 x In gives a wider gap between overload and short-circuit than a C-curve. This helps coordinate with motor starters.

MPN
MGN25087