Skip to main content
Schneider Electric ATV212HU55N4LCD

Schneider ATV212HU55N4LCD Altivar 212 VFD, 5.5 kW, 7.5 hp

MPN ATV212HU55N4LCD
Obsolete

Schneider Electric Altivar 212, variable speed drive, 5.5 kW / 7.5 hp, 380...480 V 3-phase, IP20, with integrated Class C2 EMC filter, Modbus serial, ATV212HU55N4LCD.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV212HU55N4LCD specifications
ParameterValue
Connector type1 RJ45 1 open style
Main product or component typeVariable speed drive
Voltage= 1 mOhm 500 V DC for 1 minute
Current10.9 A at 380 V 8.6 A at 480 V
Horsepower7.5 hp
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-25 °C
Temp operating max50 °C
Temp operating min-10 °C
Storage temperature-25...70 °C
Pollution degree3 conforming to IEC 61800-5-1
Depth150 mm
Width142 mm
Height184 mm
Data format8 bits, 1 stop, odd even or no configurable parity
Operating positionVertical +/- 10 degree

Product details

The Schneider ATV212HU55N4LCD is a 5.5 kW (7.5 hp) variable speed drive from the Altivar 212 series, designed for three-phase asynchronous motors on 380...480 V supplies. It draws 10.9 A at 380 V and 8.6 A at 480 V line current, with an apparent power rating of 9.1 kVA at 380 V. The integrated Class C2 EMC filter covers most industrial installations without an external filter — saves a DIN-rail slot and a wiring step. Communication is over a 2-wire RS 485 Modbus RTU link at 9600 or 19200 bps, addressing up to 247 nodes, which fits into a standard control network without a gateway. The drive includes an adjustable PI regulator for closed-loop process control (pressure, flow, level) without a separate controller. Protection covers motor and drive sides: thermal overload, short-circuit between motor phases, input phase loss, DC bus overvoltage/undervoltage, and PTC probe input for motor overtemperature.

Footprint is 184 mm high by 142 mm wide by 150 mm deep, with a heat sink on the back. Mount vertical within ±10° for proper airflow — the fan moves 74 m³/h. Leave clearance above and below for convection; the heat sink dissipates drive losses without derating up to 1000 m altitude. Above that, derate 1 % per 100 m, and for corner-grounded distribution networks limit to 2000 m. The IP20 enclosure is panel-mount only, not for washdown or outdoor use without a separate cabinet.

MPN