Schneider Electric 140AII33000 — Analog Input Modules

Schneider 140AII33000 Analog Input Module, 8 Ch, ATEX

MPN140AII33000
Obsolete

Schneider Electric Modicon Quantum 140AII33000 intrinsically safe temperature input module, 8 analog inputs, ATEX Zone 20/21/22, CE II1 G/D-EEx ia IIC marking, obsolete.

$5,076.95 – $8,594.47Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

140AII33000 key specifications
ParameterValue
Fault typeBroken wire Out of range
Type of filterPlus notch input filter 50/60 Hz thermocouple Single low pass input filter 20 Hz thermocouple
Protection typeInternal fuse
Range of productModicon Quantum automation platform
Analogue input typeLow level voltage -100...100 mV Low level voltage -25...25 mV Thermocouple - 210...760 °C thermocouple J Thermocouple - 270...1000 °C thermocouple E Thermocouple - 270...1370 °C thermocouple K Thermocouple - 270...400 °C thermocouple T Thermocouple - 50...1665 °C thermocouple R Thermocouple - 50...1665 °C thermocouple S Temperature probe - 200...850 °C Pt 100, Pt 200, Pt 500, Pt 1000 Temperature probe - 60...180 °C Ni 100, Ni 200, Ni 500, Ni 1000 Thermocouple - 130...1820 ° C thermocouple B
Product or component typeIntrinsically safe temperature input module
Measurement current0.5 mA Pt 500, Pt 1000, Ni 500, Ni 1000 2.5 mA Pt 100, Pt 200, Ni 100, Ni 200
Bus current requirement400 mA
Power dissipation in2 W
Relative humidity95 % without condensation
Operating altitude<= 16404.2 ft (5000 m)
StandardsEN 50281-1-1 EN 50014 EN 50284 CSA C22.2 No 142 EN 50020 Directive ATEX 94/9/EC EN 50039

All specifications

140AII33000 additional specifications
ParameterValue
MarkingCE II1 G/D-EEx ia IIC
Category18155-QUANTUM I/O & POWER SUPPLIES
Dust zoneOutside zone
Linearity0.003 % of full scale RTD
Resolution0.76 µV (16 bits) -25...25 mV millivolt 3.05 µV (16 bits) -100...100 mV millivolt 1 °C, 0.1 °C, 1 °F, 0.1 °F thermocouple 12 bits + sign (0.1 °C) RTD
Update time1 s TC/millivolt thermocouple 1.35 s 3 wires RTD 750 ms 2 or 4 wires RTD
Module formatStandard
Input impedance> 10 MOhm RTD thermocouple
Source resistance< 200 Ohm thermocouple
Product destinationIn conjunction with products for zone 20, 21 or 22
Measurement accuracy+/- 2 °C + 0.1 % of reading thermocouple E +/- 2 °C + 0.1 % of reading thermocouple J +/- 2 °C + 0.1 % of reading thermocouple K +/- 2 °C + 0.1 % of reading thermocouple T +/- 4 °C + 0.1 % of reading thermocouple B +/- 4 °C + 0.1 % of reading thermocouple R +/- 4 °C + 0.1 % of reading thermocouple S +/- 0.5 °C RTD 77 °F (25 °C) +/- 0.9 °C RTD 32...140 °F (0...60 °C) 20 µV + 0.1 % of reading millivolt 77 °F (25 °C)
Software designationConcept V2.2 and above Unity Pro
Analogue input number8
Common mode rejection> 100 dB 50/60 Hz RTD > 120 dB 50/60 Hz thermocouple
Hot swapping fallbackNot allowed per intrinsic safety standards
Absolute accuracy error+/- 0.05 % of full scale RTD 77 °F (25 °C) +/- 0.1 % of full scale maximum RTD 77 °F (25 °C)
Cold junction compensationInternal 32...140 °F (0...60 °C) thermocouple
Isolation between channels and bus1780 V 47...63 Hz AC for 1 minute 2500 V DC for 1 minute
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Resistance to electromagnetic fields9.1 V/m (10 V/m) 80...2000 Hz IEC 801-3
Ambient air temperature for operation32...140 °F (0...60 °C)
Resistance to electrostatic discharge4 kV contact IEC 801-2 8 kV on air IEC 801-2
Accuracy drift according to temperature0.15 mV/°C + 0.0015 % of reading/°C max thermocouple

Product details

Intrinsically safe temperature input for Modicon Quantum racks

The 140AII33000 is an intrinsically safe temperature input module that sits in a Modicon Quantum automation platform rack, handling 8 analog inputs from thermocouples (types J, K, T, E, R, S, B) and RTDs (Pt100, Pt200, Pt500, Pt1000, Ni100, Ni200, Ni500, Ni1000). It carries the CE II1 G/D-EEx ia IIC marking, meaning it is certified for use in explosive gas and dust atmospheres — Zone 20, 21, or 22 — when paired with the appropriate field devices.

The module's intrinsic safety design means hot swapping is not allowed per intrinsic safety standards — the rack must be de-energised before inserting or removing the module. Channel-to-bus isolation is rated 1780 V AC at 47–63 Hz for 1 minute and 2500 V DC for 1 minute, which keeps the hazardous-area field wiring isolated from the control bus. The input impedance is greater than 10 MOhm for both RTD and thermocouple channels, so it does not load the sensor signal. For thermocouple inputs, the source resistance must stay below 200 Ohm, and the module provides internal cold-junction compensation over 0–60 °C.

Resolution, accuracy, and update time across input types

Resolution varies by input type: 0.76 µV (16 bits) on the -25…25 mV millivolt range, 3.05 µV (16 bits) on the -100…100 mV range, 12 bits + sign (0.1 °C) for RTD, and 1 °C / 0.1 °C / 1 °F / 0.1 °F for thermocouple. Linearity is 0.003 % of full scale for RTD, and absolute accuracy at 25 °C is ±0.05 % of full scale for RTD, ±2 °C + 0.1 % of reading for types E, J, K, T thermocouples, and ±4 °C + 0.1 % of reading for types B, R, S. Update time depends on wiring: 750 ms for 2- or 4-wire RTD, 1.35 s for 3-wire RTD, and 1 s for thermocouple/millivolt inputs.

Obsolete — sourcing through independent channels

The module is available through independent surplus and broker channels.

Frequently asked questions

What is the 140AII33000's ATEX marking?

The module carries the marking CE II1 G/D-EEx ia IIC, certifying it for intrinsic safety in explosive gas and dust atmospheres, suitable for Zones 20, 21, and 22.

MPN